Cut Sheet

Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T4-47
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4.2
PLC, I/O and Communications Products
XC Series Programmable Logic Controllers
XIOC Communication Modules
Description Unit XIOC-NET-DP-M XIOC-NET-DP-S XIOC-SER XIOC-TC1
Interfaces
Interfaces PROFIBUS-DP, RS-485, EN 50170 PROFIBUS-DP, RS-485, EN 50170 RS-232(C), RS-422, RS-485 RS-232(C), RS-422, RS-485
Protocol PROFIBUS-DP master (class 1) PROFIBUS-DP slave Transparent mode, Modbus
master/slave
Transparent mode, Modbus
master/slave, DNP3 protocol
Character formats 8E1, 8O1, 8N1, 8N2, 7E2, 7O2,
7N2, 7E1
8E1, 8O1, 8N1, 8N2, 7E2, 7O2,
7N2, 7E1
Control and signal cables RTS, CTS, DTR, DSR, DCD RTS, CTS, DTR, DSR, DCD
Transfer rate kbit/s 9.6 to 12,000 9.6 to 12,000 0.3 –57.6 0.3–57.6
Potential isolation Yes Yes Yes (RS-485, RS-422) Yes (RS-485, RS-422)
Number of slaves 124
Send/receive data 3500 Byte each Max. 244 Byte 250 Byte per slave
120 Byte per slave
250/500
Bus terminating resistors Switchable Switchable Switchable for RS-485, RS-422 Switchable for RS-485, RS-422
Connector type D-sub 9-pin socket D-sub 9-pin socket RS-232: D-sub 9-pin
RS-485, 422: plug-in
terminal block
RS-232: D-sub 9-pin
RS-485, 422: plug-in
terminal block
Current consumption mA <300 <300 <275 <275
Weight kg Approx. 0.2 Approx. 0.2 Approx. 0.2 Approx. 0.2
Number of modules XC100: 1/XC200: 3 XC100: 1/XC200: 3 XC100: 2/XC200: 4 XC200: 4
Slots 1, 2, 3 1, 2, 3 Any Any