Cut Sheet

Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com V7-T4-49
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4.2
PLC, I/O and Communications Products
XC Series Programmable Logic Controllers
Power Supply Suppression Filters
General Information on Electromagnetic Compatibility (EMC) of Automation Systems
Description Unit XT-FIL-1 XT-FIL-2
General
Standards IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178
Ambient temperature °F (°C) 32° to 131° (0° to 55°) 32° to 131° (0° to 55°)
Storage °F (°C) –13° to 158° (–25° to 70°) –13° to 158° (–25° to 70°)
Mounting position Vertical or horizontal Vertical or horizontal
Vibration resistance 10–57 Hz ± 0.075 mm
57–150 Hz ± 1.0g
10–57 Hz ± 0.075 mm
57–150 Hz ± 1.0g
Mechanical shock resistance 15g/11 ms 15g/11 ms
Impact strength 500g /50 mm ±25g 500g/50 mm ±25g
Overvoltage category II II
Pollution degree 2 2
Protection type IP20 IP20
Rated impulse withstand voltage (U
imp
)V850 850
Interference immunity EN 61000-6-2 EN 61000-6-2
Weight kg 0.1 0.1
Dimensions (W x H x D) mm 35 x 90 x 30 35 x 90 x 57
Terminals Screw terminals Screw terminals
Terminal capacity
Screw terminals
Flexible with ferrule mm
2
0.2–2.5 (AWG22–12) 0.2–2.5 (AWG22–12)
Solid mm
2
0.2–2.5 (AWG22–12) 0.2–2.5 (AWG22–12)
Power Supply
Input voltage Vdc 24 24
Permissible range Vdc 20.4–28.8 20.4–28.8
Ripple %
<
5
<
5
Mains overvoltage protection Yes Yes
Potential isolation
Between input voltage and PE Yes Yes
Between input voltage and output voltage No No
Between output voltage and PE Yes Yes
Rated value Vdc 24 24
Output current A 2.2 12
Description Specification
Emitted interference EN 55011/22 Class A (VDE 0875, Part 11)
Interference immunity
ESD IEC/EN 61000-4-2 Contact discharge: 4 kV
Air discharge 8 kV
RFI IEC/EN 61000-4-3 AM (80%) 80–1000 MHz 10V/m
Mobile phones/cellphones IEC/EN 61000-4-3 PM 800–960 MHz 10V/m
Burst IEC/EN 61000-4-4 Mains/digital I/O (direct): 2 kV
Analog I/O, fieldbus (capacitive coupling): 1 kV
Surge IEC/EN 61000-4-5 Digital I/O, asymmetric, analog I/O, asymmetric, connection to shielding: 0.5 kV
Mains DC, asymmetric: 1 kV
Mains DC, symmetric: 1 kV
Mains AC, asymmetric: 0.5 kV
Mains AC, symmetric: 2 kV
Conducted interference, induced by
high-frequency fields
IEC/EN 61000-4-6; 2003 AM (80%) 150 kHz–80 MHz 3V