Cut Sheet

V7-T4-86 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—February 2014 www.eaton.com
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4.5
PLC, I/O and Communications Products
XI/ON Series Remote I/O
Relay Modules
Description Unit XN-2DO-R-NC XN-2DO-R-NO XN-2DO-R-CO
Contact type 2 NC 2 N/O 2 change-over contacts
Rated voltage at supply terminal (U
L
) Vdc 24 24 24
Rated current drawn from supply terminal (I
L
)mA
<
20
<
20
<
20
Rated current drawn from module bus (I
MB
)mA
<
28
<
28
<
28
Insulation test (U
i
) Vac 1500, 500 1500, 500 1500, 500
Heat dissipation W Normally 1 Normally 1 Normally 1
The following can be connected: Resistive loads/Inductive loads/Lamp loads
Nominal load voltage 230 Vac, 30 Vdc 230 Vac, 30 Vdc 230 Vac, 30 Vdc
Output current for channel/230 Vac
Maximum continuous current A 2 2 2
Maximum continuous current, resistive load 5A, load-dependent 5A, load-dependent 5A, load-dependent
Minimum load current mA 100 at 12 Vdc 100 at 12 Vdc 100 at 12 Vdc
Output current for DC voltage (resistive) Load limit curve, see Page V7-T4-99
Utilization factor (g) % 100 100 100
Lifespan at 230 Vac
At 5A (Operations) x 10
6
>0.1 >0.1 >0.1
At 0.5A (Operations) x 10
6
>1 >1 >1
Basic modules
Without C connection XN-S4…-SBBS XN-S4…-SBBS XN-S4…-SBBS
With C connection XN-S4…-SBCS XN-S4…-SBCS