6.1
Power Supplies
General-Purpose and Sensor Power Supplies
PSG Series, continued
Three-Phase, continued
PSG60F24RM PSG120F24RM PSG240F24RM PSG480F24RM PSG960F24RM
General/Physical Data, continued
Power derating—
vertical mounting
>50°C derate power
by 2.5% / °C,
>70°C derate power
by 5% / °C
>50°C derate power
by 2.5% / °C,
>70°C derate power
by 5% / °C
>50°C derate power
by 2.5% / °C,
>70°C derate power
by 5% / °C
>50°C derate power
by 2.5% / °C,
>70°C derate power
by 5% / °C
>50°C derate power
by 2.5% / °C
Power derating—
horizontal mounting
>45°C derate power
by 2.5% / °C,
>55°C derate power
by 1.66% / °C,
>70°C derate power
by 5% / °C
>40°C derate power
by 2.5% / °C,
>60°C derate power
by 5% / °C
>40°C derate power
by 2.5% / °C,
>60°C derate power
by 5% / °C
N/A N/A
Operating humidity <95% RH, noncondensing <95% RH, noncondensing <95% RH, noncondensing 5 to 95% RH, noncondensing 5 to 95% RH, noncondensing
Vibration 10 to 500 Hz, 0.35 mm acc. 30 m/s
2
, single amplitude (3G max.) for 60 min. in each X, Y and Z directions, in accordance with IEC 60068-2-6
Pollution degree22222
Climatic class 3K3 according to EN 60721 3K3 according to EN 60721 3K3 according to EN 60721 3K3 according to EN 60721 3K3 according to EN 60721
Safety and Protection
Transient surge voltage Varistor Varistor Varistor Varistor Varistor
Surge voltage protection against
internal surge
Yes Yes Yes Yes Yes
Safety class Class I with ground connection Class I with ground connection Class I with ground connection Class I with ground connection Class I with ground connection
Shock 30G (300 m/s
2
) in all directions
according to IEC60068-2-27
30G (300 m/s
2
) in all directions
according to IEC60068-2-27
30G (300 m/s
2
) in all directions
according to IEC60068-2-27
30G (300 m/s
2
) in all directions
according to IEC60068-2-27
30G (300 m/s
2
) in all directions
according to IEC60068-2-27