Industrial Control Transformers
Trans for mers
Accessories
Primary Fuse Kit
The primary fuse kit includes a two-pole class CC fuse block,
instructions, and all associated mounting and wiring hardware.
Fuses are not included. When installed, the primary fuse kit
will add a maximum of 11/16 inch to the transformer depth
and 1-15/16 inches to the transformer height.
Primary Fuse Kit
Finger-Safe Terminal Covers (Optional)
Fits CE Marked designs 50–750 VA
Fits MTE designs 0.25–750 VA
Finger-Safe Terminal Covers
Finger-Safe Primary Fuse Block Covers
Fits two-pole primary fuse blocks on MTE designs
No fuse block covers are available for transformers with
suffix “FBQ”
Finger-Safe Primary Fuse Block Covers
Secondary Fuse Clip Cover
Secondary Fuse Clip Cover
Technical Data and Specifications
Insulation System and Temperature Rise
Industry standards classify insulation systems and rise as
shown below:
Insulation System Classification
The design life of transformers having different insulation
systems is the same—the lower-temperature systems are
designed for the same life as the higher-temperature systems.
Series-Multiple Windings
Series-multiple windings consist of two similar coils in each
winding that can be connected in series or parallel (multiple).
Transformers with series-multiple windings are designated with
an “x” or “/” between the voltage ratings, such as voltages of
“120/240” or “240 x 480.” If the series-multiple winding is
designated by an “x,” the winding can be connected only
for a series or parallel. With the “/” designation, a mid-point
also becomes available in addition to the series or parallel
connection. As an example, a 120 x 240 winding can be
connected for either 120 (parallel) or 240 (series), but a
120/240 winding can be connected for 120 (parallel),
240 (series) or 240 with a 120 mid-point.
For additional information, please refer to Volume 2,
CA08100003E.
Description Catalog Number
Primary fuse kit PFK1
Description Catalog Number
Four terminal transformers FSK4
Four terminal Series 2 transformers only FSK4S2
Six terminal transformers FSK6
Description Catalog Number
Primary fuse block covers FSKFB
Description Catalog Number
Fits 500 VA and smaller models SFCS
Fits models greater than 500 VA SFCL
FSK4
FSK6
FSKFB
Ambient + Winding Rise + Hot Spot = Temp. Class
40°C 55°C 10°C 105°C
40°C 80°C 30°C 150°C
25°C 135°C 20°C 180°C
40°C 115°C 30°C 185°C
40°C 150°C 30°C 220°C