Cut Sheet

Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—July 2015 www.eaton.com V7-T9-19
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT In-Panel and On-Machine Wiring Solution
Contactor Modules
Product Selection
Contactor Modules
123
SmartWire-DT module for attachment to XTCE007–XTCE032 contactors and XTRE control relays.
One module is required per contactor.
PKE Contactor Module
SmartWire-DT module for connection of XTPE manual motor controllers.
One module is required per contactor and XTPE manual motor protector.
Design Note
The number of motor starters or XTCE contactors that can be connected is dependent
upon the power consumption of the contactor coils. To increase the number of
SmartWire-DT modules that can be connected. Powerfeed modules can be used.
Notes
1
Take account of the maximum current consumption of the contactor coils per SmartWire-DT line.
2
A2 connections must not be linked.
3
Connection terminals for electrical interlocking are not suitable for safety technology.
Description Pkg. Qty. Catalog Number
Two digital inputs for voltage-free contacts.
One electrical interlock for the surface mounting of reversing combinations.
Messages: Switch status contactor, status of the digital inputs 1 and 2.
Commands: Contactor actuation.
5 DIL-SWD-32-001
Two digital inputs for voltage-free contacts.
One electrical interlock for the surface mounting of reversing combinations.
1-0-A switch for manual or automatic operation.
Messages: Contactor switching position, status of the digital inputs 1 and 2, 1-0-A switch position.
Commands: Contactor actuation.
5 DIL-SWD-32-002
Description Pkg. Qty. Catalog Number
Connecting cable between module and XTPE trip block included as standard.
One electrical interlock for the surface mounting of reversing starters.
1-0-A switch for manual or automatic operation.
Selectable overload relay function for connecting the contactor on overload.
Messages:
Switch position contactor/PKE/1-0-A switch
Motor current in %
Thermal motor image in %
Trip-indicating auxiliary contact (Overload, Short-circuit,...)
Set value of overload releases
Set value Verification time (CLASS), Part no. Trip block.
Commands: Contactor actuation, activation of overload relay function (ZMR)
4 PKE-SWD-32
24 Vdc XTCE007 XTCE009 XTCE012 XTCE015 XTCE018 XTCE025 XTCE032
Pick-up power W 3 3 4.5 4.5 12 12 12
Sealing power W 3 3 4.5 4.5 0.5 0.5 0.5
Contactor Modules
PKE Contactor Module