Cut Sheet

V7-T9-38 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—July 2015 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT In-Panel and On-Machine Wiring Solution
Technical Data and Specifications
Gateway Modules
Note
1
If contactors with a total current consumption >3 A are connected, a powerfeed module EU5C-SWD-PF1/2 has to be used.
Description Unit
EU5C-SWD-
EIP-MODTCP
Gateway
EU5C-SWD-
PROFINET
Gateway
EU5C-SWD-DP
Gateway
EU5C-SWD-
ETHERCAT
Gateway
EU5C-SWD-CAN
Gateway
EU5C-SWD-
POWERLINK
Gateway
General
Standards IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
IEC/EN 61131-2
EN 50178
Dimensions (W x H x D) in
(mm)
1.38 x 3.54 x 4.88
(35 x 90 x 124)
1.38 x 3.54 x 4.88
(35 x 90 x 124)
1.38 x 3.54 x 5.0
(35 x 90 x 127)
1.38 x 3.54 x 5.0
(35 x 90 x 127)
1.38 x 3.54 x 5.0
(35 x 90 x 127)
1.38 x 3.54 x 5.0
(35 x 90 x 127)
Weight lbs (kg) 0.37 (0.17) 0.37 (0.17) 0.35 (0.16) 0.35 (0.16) 0.35 (0.16) 0.35 (0.16)
Mounting DIN rail IEC/EN 60715, 35 mm DIN rail IEC/EN 60715, 35 mm DIN rail IEC/EN 60715, 35 mm
Mounting position Vertical Vertical Vertical Vertical Vertical Vertical
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP20 IP20 IP20 IP20 IP20 IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4 5–8.4 5–8.4 5–8.4
Constant acceleration 1 g Hz 8.4–150 8.4–150 8.4–150 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15 g/11 ms
Impacts 9 9 9 9 9 9
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category II II II II II II
Pollution degree 2 2 2 2 2 2
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8 8 8 8 8 8
Contact discharge (Level 2) kV 4 4 4 4 4 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10 10 10 10 10
1.4–2 GHz V/m 3 3 3 3 3 3
2–2.7 GHz V/m 1 1 1 1 1 1
Radio interference suppression (SmartWire-DT) EN 55011 Class A EN 55011 Class A EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables kV 2 2 2 2 2 2
CAN/DP bus cable kV 1 1 1 1 1 1
SmartWire-DT cables kV 1 1 1 1 1 1
Surge (IEC/EN 61131-2:2008, Level 1)
Supply cables kV 0.5 0.5 0.5 0.5 0.5 0.5
CAN/DP bus cable kV 1 1 1 1 1 1
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10 10 10 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°)
Condensation Prevent with suitable measures Prevent with suitable measures Prevent with suitable measures
Storage °F (°C) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°)
Relative humidity, noncondensing (IEC/EN 60068-2-30) % 5–95 5–95 5–95 5–95 5–95 5–95
Supply Voltage U
Aux
SM Puffer Bremer V 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%)
Residual ripple on the input voltage %
<
5
<
55555
Protection against polarity reversal Yes Yes Yes Yes Yes Yes
Max. current (I
max
)A3
1
3
1
3
1
3
1
3
1
3
1
Short-circuit rating No, external fuse FAZ Z3 No, external fuse FAZ Z3 No, external fuse FAZ Z3
Power loss W Normally 1 Normally 1 Normally 1 Normally 1 Normally 1 Normally 1
Potential isolation No No No No No No
Rated operating voltage of 24 Vdc modes V Typ. U
Aux
–0.2 Typ. U
Aux
–0.2 Typ. U
Aux
–0.2 Typ. U
Aux
–0.2 Typ. U
Aux
–0.2 Typ. U
Aux
–0.2