9.1
Connectivity Solutions
SmartWire-DT In-Panel and On-Machine Wiring Solution
Digital I/O Modules, continued
Note
1
Three-wire connection with power supply l+, l-.
Description Unit EU5E-SWD-8DX EU5E-SWD-4DX EU5E-SWD-4D4D EU5E-SWD-4D2R EU5E-SWD-X8D
Connection Supply and I/O
Connection type Push in terminals Push in terminals Push in terminals Push in terminals Push in terminals
Solid mm
2
0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16) 0.2–1.5 (AWG 24–16)
Flexible with ferrule
1
mm
2
0.25–1.5 (AWG 24–16) 0.25–1.5 0.25–1.5 0.25–1.5 0.25–1.5 (AWG 24–16)
24 Vdc Supply for Output Supply
Rated operational voltage (U
e
) V 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%) 24 Vdc (–15%/+20%)
Residual ripple on the input voltage %
<
55
<
5
Protection against polarity reversal Yes Yes Yes
Digital Inputs
Quantity 8 4
1
44—
Input current mA Typ. 4 at 24 Vdc Typ. 4 at 24 Vdc Typ. 4 at 24 Vdc Typ. 4 at 24 Vdc Typ. 4 at 24 Vdc
Voltage level to IEC/EN 61131-2
Limit value type 1 Low <5 Vdc; High >15 Vdc
Input delay
High <0.2 ms <0.2 ms <0.2 ms <0.2 ms <0.2 ms
Low <0.2 ms <0.2 ms <0.2 ms <0.2 ms <0.2 ms
SmartWire-DT status (LED) Yellow Yellow Yellow Yellow
Power Supply l+, l-
Overload proof Yes, with diagnostics
Output current per input supply A
<
0.5———
Supply voltage V U
e
0.16 V
Transistor Outputs
Number ——4 —8
Output current A Normally 0.5 at 24 Vdc Normally 0.5 at 24 Vdc
Short-circuit tripping current A Max. 1.2 over 3 ms Max. 1.2 over 3 ms
Lamp load (R
LL
) W——3
<
3
Overload proof Yes, with diagnostics Yes, with diagnostics
Switching capacity EN 60947-5-1 utilization
category DC-13
EN 60947-5-1 utilization
category DC-13
Status display LED————Yellow
Relay Outputs
Number ———2
Contact type art ———N/O contact
Operations
Utilization category AC-1, 250 V, 6 A >6 x 10
4
Utilization category AC-15, 250 V, 3 A ———>5 x 10
4
Utilization category DC-13, 24 V, 1 A ———>2 x 10
5
Safe isolation Vac———230
Minimum load current mA ———100 mA, 12 Vdc
Pick-up/drop-out time ms———5/2.5
Bounce duration ms———Normally 1.5
Short-circuit protection ———External 4A gL/gG
Status display outputs (LED) Yellow Yellow
Potential Isolation
Inputs for SmartWire-DT Yes Yes Yes Yes Yes
Transistor outputs for SmartWire-DT Yes Yes
Transistor outputs for inputs No
Relays for SmartWire-DT ———Yes
Relays for inputs ———Yes
Relays for relays ———Yes