Connectivity Solutions
SmartWire-DT In-Panel and On-Machine Wiring Solution
Analog I/O Modules
Note
1
Minimum length 8 mm.
Description Unit EU5E-SWD-4AX EU5E-SWD-2A2A EU5E-SWD-4PT EU5E-SWD-4PT-2
General
Standards IEC/EN 61131-2/EN 50178 IEC/EN 61131-2/EN 50178 IEC/EN 61131-2/EN 50178 IEC/EN 61131-2/EN 50178
Dimensions (W x H x D) in (mm) 1.38 x 3.54 x 3.97 (35 x 90 x 101) 1.38 x 3.54 x 3.97 (35 x 90 x 101) 1.38 x 3.54 x 3.97 (35 x 90 x 101) 1.38 x 3.54 x 3.97 (35 x 90 x 101)
Weight lbs (kg) 0.22 (0.10) 0.22 (0.10) 0.22 (0.10) 0.22 (0.10)
Mounting Top-hat rail IEC/EN 60715, 35 mm Top-hat rail IEC/EN 60715, 35 mm Top-hat rail IEC/EN 60715, 35 mm Top-hat rail IEC/EN 60715, 35 mm
Mounting position Vertical Vertical Vertical Vertical
Ambient Conditions, Mechanical
Protection type (IEC/EN 60529) IP20 IP20 IP20 IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4 5–8.4
Constant acceleration 1 g Hz 8.4–150 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN
60068-2-27)
semi-sinusoidal 15 g/11 ms
Impacts 9 9 9 9
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50) 1.97 (50) 1.97 (50) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category II II II II
Pollution degree 2 2 2 2
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8 8 8 8
Contact discharge (Level 2) kV 4 4 4 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10 10 10
1.4–2 GHz V/m 3 3 3 3
2–2.7 GHz V/m 1 1 1 1
Radio interference suppression (SmartWire-DT) EN 55011 Class A EN 55011 Class A EN 55011 Class A EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables kV 2 2 2 2
Signal lines kV 2 2 2 2
SmartWire-DT cables kV 2 2 2 2
Surge (IEC/EN 61131-2:2008, Level 1) Supply cables 1.0 kV Supply cables 1.0 kV Supply cables 1.0 kV Supply cables 1.0 kV
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) 13° to 131° (–25° to 55°) 13° to 131° (–25° to 55°) 13° to 131° (–25° to 55°) 13° to 131° (–25° to 55°)
Condensation Prevent with suitable measures Prevent with suitable measures Prevent with suitable measures Prevent with suitable measures
Storage °F (°C) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°)
Relative humidity, noncondensing
(IEC/EN 60068-2-30)
% 5–95 5–95 5–95 5–95
SmartWire-DT Network
Station type SmartWire-DT slave SmartWire-DT slave SmartWire-DT slave SmartWire-DT slave
Baud rate setting Automatic Automatic Automatic Automatic
SmartWire-DT status LED LED Green Green Green Green
Connection Plug: 8-pole/Connection plug: External device plug SWD4-8SF2-5
Current consumption (15 V SWD supply) See Page V7-T9-61 See Page V7-T9-61 See Page V7-T9-61 See Page V7-T9-61
Connection Supply and I/O
Connection type Push in terminals Push in terminals Push in terminals Push in terminals
Solid mm
2
0.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16)
Flexible with ferrule
1
mm
2
0.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16) 0.25–1.5 (AWG 24–16)
24 Vdc Supply for Output Supply
Rated operational voltage (U
e
) V 24 Vdc –15%/+20% 24 Vdc –15%/+20% 24 Vdc –15%/+20% 24 Vdc –15%/+20%
Residual ripple on the input voltage %
<
5
<
5
<
5
<
5
Current consumption mA 10 50
Protection against polarity reversal Yes Yes Yes Yes