9.1
Connectivity Solutions
SmartWire-DT In-Panel and On-Machine Wiring Solution
Accessories
Description Unit
SWD4-RC8-10
Resistor
SWD4-8SF2-5
Plug
SWD4-8SFF2-5
Coupling
SWD4-SF8-20
Bushing
General
Standards IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178
Dimensions (W x H x D) in
(mm)
1.91 x 1.36 x 0.34
(48.5 x 34.5 x 10)
0.59 x 1.44 x 0.69
(15 x 36.5 x 17.5)
1.91 x 1.36 x 0.34
(48.5 x 34.5 x 10)
0.94 x 1.02 x 6.34
(24 x 26 x 162)
Weight lbs (g) 0.022 (10) 0.012.1 (5.5) 0.010 (4.5) 0.044 (20)
Mounting position As required As required As required As required
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP20 IP20 IP20 IP67
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4
Constant acceleration 1 g Hz 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15 g/11 ms
Impacts999—
Drop to IEC/EN 60068-2-31 (drop height) in (mm) 1.97 (50)
Free fall, packaged (IEC/EN 60068-2-32) ft (m) 1.0 (0.3)
Electromagnetic Compatibility (EMC)
Overvoltage category II
Pollution degree 2
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8
Contact discharge (Level 2) kV 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10
1.4–2 GHz V/m 3
2–2.7 GHz V/m 1
Radio interference suppression (SmartWire-DT) EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
SmartWire-DT cables kV 1
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°)
Condensation Prevent with suitable measures
Storage °F (°C) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°)
Relative humidity, noncondensing (IEC/EN 60068-2-30) % 5 –95 5 –95 5 –95 5 –95
Connection Options
SWD-In Plug, 8-pole Plug connector Plug, 8-pole
Number of insertion cycles
>
200 1
>
200
SWD-Out Socket, 8-pole Plug, 8-pole Socket, 8-pole
Number of insertion cycles
>
200
>
200
>
500
Current consumption (15 V SWD supply) See Page V7-T9-61 See Page V7-T9-61 See Page V7-T9-61 See Page V7-T9-61