Cut Sheet

V7-T9-48 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—July 2015 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT In-Panel and On-Machine Wiring Solution
Accessories, continued
Description Unit
SWD4-SM8-20
Bushing
SWD4-8FRF-10
Adapter
SWD4-SFL8-20
Adapter
SWD4-SML8-20
Adapter
General
Standards IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178 IEC/EN 61131-2; EN 50178
Dimensions (W x H x D) in
(mm)
0.94 x 1.02 x 6.69
(24 x 26 x 170)
1.38 x 3.54 x 1.38
(35 x 90 x 35)
1.38 x 3.27 x 1.57
(35 x 83 x 40)
1.38 x 3.27 x 1.82
(35 x 83 x 46)
Weight lbs (g) 0.050 (22.5) 0.093 (42) 0.110 (50) 0.110 (50)
Mounting position As required As required As required As required
Ambient Conditions, Mechanical
Degree of protection (IEC/EN 60529) IP67 IP20 IP67 IP67
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm Hz 5–8.4 5–8.4 5–8.4
Constant acceleration 1 g Hz 8.4–150 8.4–150 8.4–150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15 g/11 ms
Impacts 9 9 9
Drop to IEC/EN 60068-2-31 (drop height) in (mm) ————
Free fall, packaged (IEC/EN 60068-2-32) ft (m) ————
Electromagnetic Compatibility (EMC)
Overvoltage category ————
Pollution degree ————
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8 8 8
Contact discharge (Level 2) kV 4 4 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80–1000 MHz V/m 10 10
1.4–2 GHz V/m 3 3
2–2.7 GHz V/m 1 1
Radio interference suppression (SmartWire-DT) ————
Burst (IEC/EN 61131-2:2008, Level 3) ————
SmartWire-DT cables kV————
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 10
Climatic Environmental Conditions
Operating ambient temperature (IEC 60068-2) °F (°C) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°) –13° to 131° (–25° to 55°)
Condensation Prevent with suitable measures
Storage °F (°C) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°) –40° to 158° (–40° to 70°)
Relative humidity, noncondensing (IEC/EN 60068-2-30) % 5–95 5–95 5–95 5–95
Connection Options
SWD-In Plug, 8-pole Plug, 8-pole Plug, 8-pole Plug, 8-pole
Number of insertion cycles
>
500
>
200
>
200
>
500
SWD-Out Push in terminals Socket, 8-pole Plug, 8-pole
Number of insertion cycles
>
500
>
200
Current consumption (15 V SWD supply) See Page V7-T9-61 See Page V7-T9-61 See Page V7-T9-61 See Page V7-T9-61