Cut Sheet

V7-T9-50 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—July 2015 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.1
Connectivity Solutions
SmartWire-DT In-Panel and On-Machine Wiring Solution
Machine Mount I/O Modules, continued
Description Unit EU1E-SWD-2DX EU1E-SWD-2DD EU2E-SWD-4DX EU2E-SWD-4DD
SmartWire-DT Network
Stations type SmartWire-DT slave SmartWire-DT slave SmartWire-DT slave SmartWire-DT slave
Baud rate setting Automatic Automatic Automatic Automatic
Maximum Bit/sec2 M2 M2 M2 M
SW-DT status LED Green (625 nm) Green (625 nm) Green (625 nm) Green (625 nm)
Connectors (IEC-61076-2-101) M12 A
coding
SW-DT network input connector M12-M / 5-pole M12-M / 5-pole M12-M / 5-pole M12-M / 5-pole
Pin 1 24 Vdc 24 Vdc 24 Vdc 24 Vdc
Pin 2 Data A Data A Data A Data A
Pin 3 GND GND GND GND
Pin 4 Data B Data B Data B Data B
Pin 5 SEL (IN) SEL (IN) SEL (IN) SEL (IN)
SW-DT network output connector M12-F / 5-pole M12-F / 5-pole M12-F / 5-pole M12-F / 5-pole
Pin 1 24 Vdc 24 Vdc 24 Vdc 24 Vdc
Pin 2 Data A Data A Data A Data A
Pin 3 GND GND GND GND
Pin 4 Data B Data B Data B Data B
Pin 5 SEL (OUT) SEL (OUT) SEL (OUT) SEL (OUT)
24 Vdc Power (SWD-T Bus 24 Vdc)
Rated operational voltage V / Ue 24 V –15% +20% 24 V –15% +20% 24 V –15% +20% 24 V –15% +20%
Residual ripple on the input voltage % ≤5 ≤5 ≤5 ≤5
Reverse Polarity Protection Yes Yes yes yes
Rated supply current mA 55 58 75 TBD
Digital Inputs
Input current mA Nominal 4 at 24 Vdc Nominal 4 at 24 Vdc Nominal 4 at 24 Vdc Nominal 4 at 24 Vdc
Voltage level to (IEC/EN 61131-2)
Limit value type 1 L < 5 Vdc; H > 15 Vdc L < 5 Vdc; H > 15 Vdc L < 5 Vdc; H > 15 Vdc L < 5 Vdc; H > 15 Vdc
Input delay H->L or L->H < 0.2 ms H->L or L->H < 0.2 ms H->L or L->H < 0.2 ms H->L or L->H < 0.2 ms
Status display LED Yellow Yellow Yellow Yellow
Digital Outputs
Output driver circuit power source Bus/Ext Bus Bus
Output current A 0.5 at 24 Vdc 0.5 at 24 Vdc
Trip current SC A 1.2 over 3 ms 1.2 over 3 ms
Lamp load W ≤3 ≤3
Overload proof (IEC/EN 61131-2) Yes w/diag Yes w/diag
Switching capacity IEC 60947-5-1 DC-13 DC-13
Status display LED Yellow Yellow
Total current all outputs A 1 2