1.2
Solar Power Center Loadcenters and Meter Breakers
Application Description
How to Size a Solar-Ready
Loadcenter or a Meter Breaker
for your Solar Application
The National Electrical Code
(2008) Section 690.64(B)(2)/
(2011) Section 705.12(D)(2)
states: “The sum of the
ampere ratings of overcurrent
devices in circuits supplying
power to a busbar or
conductor shall not exceed
120 percent of the rating of
the busbar or conductor.”
For example: A 200A main
breaker loadcenter + a
backfed 70A PV breaker =
270A = 120% of the 225A
busbar rating. In 2014, 120%
was extended to 125% of the
conductor rating.
Note: Check with local utility for
exact requirements.
Features and Benefits
Solar Power Center
Up to 225A rated copper
bussing maximizes solar
source up to 70A for
standard units
100A, 125A and 200A main
breakers available factory
installed, which provides
additional flexibility in
PV sizing
Main breaker and PV
backfed main are located
at opposite ends of the
distribution panel
Single-phase, three-wire
120/240 Vac
Overhead and underground
feed applications
Padlocking provisions
Surface and flush designs
available
Top or bottom exit of
load wiring
Limited lifetime warranty
for Type CH and 10-year
warranty for Type BR
Loadcenters
Type CH features plug-on
neutral loadcenters and
breakers that enable the
contractor to connect the
breaker directly to the
neutral bar, eliminating the
need for wiring a pigtail
Type CH features unique
stab design, which
provides a tight connection
to the bus
Top or bottom feed
Straight-in wiring saves
labor and material
Only one panel for either
application—no
modifications necessary
Extra 1.50-inch (38.1 mm)
knockout for bundling
enables easier installation
Drywall marking on
enclosure indicates proper
mounting depth for flush
applications
Unique sandalwood finish
is aesthetically appealing
with scratch-resistant
powder coating
Silver flash plated copper
bus provides superior
conductivity
Meter Breakers
Meter socket and
distribution section are
located in one enclosure,
which provides labor and
material savings
EUSERC / West Coast and
Non-EUSERC designs
Ring, ringless and lever
bypass designs
7-inch-deep designs
available, which is ideal for
stucco homes
Endwall knockouts are
easily accessible for future
wiring without damaging
stucco
Standards and Certifications
Complies with NEC (2008)
Section 690.64(B) / (2011)
Section 705.12(D), which
identifies the acceptable
installation and marking
requirements for utility
interactive solar inverters
UL Listed
Non-EUSERC
EUSERC/West Coast
Panel Main Breaker
Ampere Rating
Standard Bus
Ampere Rating
Maximum Total Ampere Rating of
all PV Backfed Mains
Maximum Ampere Rating of
Panel Mains + PV Mains
100 100 20 120
100 125 50 150
125 125 25 150
200 200 40 240
200 225 70 270
225 225 45 270
400 400 80 480