Installation Manual

MN04001003E 2 February 2006
Hazardous High Voltage
WARNING
Motor control equipment and electronic controllers are connected to hazardous line voltages. When servicing drives
and electronic controllers, there may be exposed components with housings or protrusions at or above line
potential. Extreme care should be taken to protect against shock.
Stand on an insulating pad and make it a habit to use only one hand when checking components.
Always work with another person in case an emergency occurs.
Disconnect power before checking controllers or performing maintenance.
Be sure equipment is properly grounded.
Wear safety glasses whenever working on electronic controllers or rotating machinery.
Power and Control Wiring
Basic Wiring
Use power terminals R/L1 and S/L2 for single-phase connection to models: NFXF25A0-1, NFXF50A0-1,
NFXF25A0-2, NFXF50A0-2 or NFX001A0-2.
Use power terminals R/L1, S/L2 and T/L3 for three-phase connection to models: NFXF25A0-2, NFXF50A0-2,
NFX001A0-2 or NFX002A0-2.
Single-phase power must not be used for model NFX002A0-2.
Main Circuit Wiring
Wire Type: 75°C Copper Only
Catalog
Number Voltage / Horsepower
Max. Current (A)
(Input/Output)
Wire Gauge
(AWG)
Torque Rating
(kgf-cm)
NFXF25A0-1 (1-phase)
NFXF50A0-1 (1-phase)
115V AC, 1/4 hp
115V AC, 1/2 hp
6.0/1.6
9.0/2.5
12 – 16
12 – 14
5
NFXF25A0-2 (1-phase)
NFXF50A0-2 (1-phase)
NFX001A0-2 (1-phase)
230V AC, 1/4 hp
230V AC, 1/2 hp
230V AC, 1 hp
4.9/1.6
6.5/2.5
9.7/4.2
12 – 16
12 – 16
12 – 14
5
NFX002A0-2 (3-phase) 230V AC, 2 hp 9.0/7.0 12 – 14 5
Single-Phase Models
Input from R/L1, S/L2
LED Display
AC Line
Input
Te rm inals
Grounding
Frequency
Setting Knob
RUN/STOP
Signal Selection
for AVI to Input
DC0 to +10V or
4 to 20 mA
Control Terminal
RS-485
Communication
Port
Motor Capacity
and Input Power
Data Confirmation
Key
Function Display
Key
UP/DOWN
Grounding
Motor
Connections
Wire Gauge: 12 – 20 AWG
Torque: 5 Kgf-cm
Wire Gauge: 12 – 20 AWG
Torque: 5 Kgf-cm
RA RC +10V AVI D1
U/T1 V/T2 W/T3
R/L1 S/L2 T/L3
D2 D3 D4 GND
STOP
RUN
FWD
REV
RUN
STOP
ENTER
MODE
RESET
WARNING
MIN. MAX.
NFX9000
RS-485
230V 1 PHASE
0.5 HP
!
MN04001003E.fm Page 2 Tuesday, March 21, 2006 8:26 AM