Group 4 — Input Function Parameters, continued
Group 5 — Multi-Step Speed and PLC Parameters
Group 6 — Protection Parameters
Code Parameter Min. Max. Unit Default Note
4-05 Digital Input 3 (D3)
Note: Setting
parameter 4-04 to
value 3 presets D3 to
3-wire operation
0, 4 20 6
0:
Not used
4:
External fault, normally open (NO)
5:
External fault, normally closed (NC)
6:
Reset
7:
Multi-step speed command 1
8:
Multi-step speed command 2
9:
Jog operation
10:
Accel./decel. speed inhibit
11:
First or second accel./decel. time selection
12:
Base block, NO
13:
Base block, NC
14:
Increase master frequency
15:
Decrease master frequency
16:
Run PLC program
17:
Pause PLC
18:
Counter trigger signal
19:
Counter reset
20:
Select ACI/deselect AVI
4-06 Digital Input 4 (D4) 0, 4 20 7 Same as 4-05.
Code Parameter Min. Max. Unit Default Note
5-00 First step speed
frequency
0.0 400 Hz 0 0 – 400 Hz
5-01 Second step speed
frequency
0.0 400 Hz 0 0 – 400 Hz
5-02 Third step speed
frequency
0.0 400 Hz 0 0 – 400 Hz
5-03 PLC mode 0 4 0
0:
Disable PLC operation
1:
Execute one program cycle
2:
Continuously execute program cycles
3:
Execute one program cycle step by step (separate by
STOP)
4:
Continuously execute one program cycle step by
step (separate by STOP)
5-04 PLC forward/reverse
motion
0 1 0 0 – 15
0:
Forward
1:
Reverse
5-05 Time duration step 0 0 65500 sec. 0 0 – 65500 seconds
5-06 Time duration step 1 0 65500 sec. 0 0 – 65500 seconds
5-07 Time duration step 2 0 65500 sec. 0 0 – 65500 seconds
5-08 Time duration step 3 0 65500 sec. 0 0 – 65500 seconds
Code Parameter Min. Max. Unit Default Note
6-00 Over-voltage
prevention level
0 410 V 390
0:
Disable, 350 – 410V
6-01 Over-current
prevention level
0 200 % 170
0:
Disable, 20 – 200%
6-02 Over-torque
detection
04 0
0:
Disable
1:
Enabled during constant speed operation; continues
until the continuous limit is reached
2:
Enabled during constant speed operation; halted
after detection
3:
Enabled during acceleration; continues before
continuous output time limit is reached
4:
Enabled during acceleration; halted after over-torque
detection
6-03 Over-torque
detection level
30 200 % 150 30 – 200%
6-04 Over-torque
detection time
0.1 10.0 sec. 0.1 0.1 – 10.0 seconds
6-05 Electronic thermal
overload relay
02 0
0:
Not used
1:
Act with standard motor
2:
Act with special motor
6-06 Electronic thermal
characteristic
30 600 sec. 60 30 – 600 seconds