Datasheet
03/20/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 5
General
Standards IEC/EN 60 947, VDE 0660, IEC/EN 60 204, CSA,UL Switch-disconnectors
to IEC/EN 60 947-3
NEMA3R, NEMA12, NEMA13
Lifespan, mechanical Operations x
10
6
0.1
Maximum operating frequency Operations/
h
50
Climatic proofing Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC
60068-2-30
Ambient temperature °C
Open °C - 25 - 50
Enclosed °C - 25 - 40
Mounting position As required
Mechanical shock resistance to IEC 60068-2-27 Half-
sinusoidal
shock
20 ms
g > 15
Contacts
Rated operational voltage U
e
V
AC
690
Rated impulse withstand voltage U
imp
V
AC
6000
Overvoltage category/pollution degree III/3
Rated uninterrupted current I
u
A
open I
u
A 63
Enclosed I
u
A 63
Load rating with intermittent operation, class 12
AB 25 % DF x I
e
2
AB 40 % DF x I
e
1.6
AB 60 % DF x I
e
1.3
Short-circuit rating
Fuse A
gG/
gL
80
Rated short-time withstand current (1 s current) I
cw
A
rms
1260
Switching angles ° 90
Current heat loss per contact at I
e
W 4.5
Terminal�capacities
Solid or stranded
mm
2
1 x (2.5 - 35)
2 x (2.5 - 10)
Flexible with ferrule to DIN 46228
mm
2
1 x (1.5 - 25)
2 x (1.5 - 6)
Terminal screw M5
Tightening torque Nm 3
Switching�capacity
AC x U
s
Rated making capacity cos ϕ = 0.35 A 800
Rated breaking capacity, motor load switch cos ϕ = 0.35 A
230 V A 640
400 V A 600
500 V A 590
690 V A 340
Rated operational current 440 V load-break switch AC-21A I
e
A 63
Rating, AC-3 motor load switch P kW
220/230 V P kW 15
400 V P kW 30
500 V P kW 30
690 V P kW 20
AC-23A Motor load switches (main switches maintenance switches) P kW
230 V P kW 18.5