Physical data (continued)
End cable tap box (Figure 27)
End cable tap boxes are used to feed a run of busway with cable
and conduit or where loads served by busway are connected
without the need for overcurrent protection. For indoor applications,
the “T” side, side opposite “T,” and the end panel are removable
for access to the lugs. For outdoor applications, these panels are
gasketed to prevent moisture from entering. In addition, the
outdoor end cable tap boxes are provided with removable gasketed
side access panels located on the “F” and side opposite “F” for
more accessibility to the lugs. Removable side access panels are
available on indoor cable tap boxes upon request.
ote:N All dimensions are to the centerline of the Pow-R-Bridge.
“T” Side
Removable
Indoor
12.00
(304.8)
Side Opposite “T”
Removable Indoor
17.50
(444.5)
15.00
(381.0)
Gasketed
Access Cover
on Front and
Back of Box
for Outdoor
Tap Boxes
Standard
32.50
(825.5)
30.00
(762.0)
38.00
(965.2)
D
Min.
Gutter
Space
of
Duct
L
C
L
C
A
(Minimum)
Figure 27. End cable tap box
a
Dimension D: For mechanical lugs = 21.34 inches (542.0 mm).
For compression lugs = 19.44 inches (493.8 mm).
b
200% neutral.
Table 35. End cable tap box dimension
Copper Aluminum
Quantity of mechanical terminals, range—one #4 (20 mm
2
)—
600 kcmil (300 mm
2
), two 1/0 (50 mm
2
)–250 kcmil (120 mm
2
)
a
UL 857
ampere rating
Dimension A
in inches (mm)
b
UL 857
ampere rating
Dimension A
in inches (mm)
b
Copper Aluminum
G
c
P
d
N
e
G
c
P
d
N
e
225 12.00 (304.8) 225 12.00 (304.8) 1 2 4 1 2 4
400 12.00 (304.8) 400 12.00 (304.8) 1 2 4 1 2 4
600 12.00 (304.8) 600 12.00 (304.8) 1 2 4
800 12.00 (304.8) 12.00 (304.8) 2 3 5 1 2 4
1000 12.00 (304.8) 12.00 (304.8) 2 3 6
1200 12.00 (304.8) 800 12.00 (304.8) 2 4 8 2 3 5
1350 12.00 (304.8) 1000 12.00 (304.8) 2 4 8 2 3 6
1600 20.50 (520.7) 1200 12.00 (304.8) 3 5 9 2 4 8
2000 20.50 (520.7) 1350 20.50 (520.7) 3 6 12 2 8
1600 24.50 (622.3) 3 5 9
2500 24.50 (622.3) 2000 24.50 (622.3) 4 8 16 3 6 12
3200 30.50 (774.5) 5 9 18
4000 45.00 (1143.0) 2500 30.50 (774.5) 6 12 24 4 8 16
3200 30.50 (774.5) 5 9 18
5000 45.00 (1143.0) 4000 45.00 (1143.0) 7 15 30 6 12 24
a
For compression lugs, factory provides provisions only.
b
All dimensions shown in Figure 27 remain constant regardless of system wiring configuration.
c
Denotes quantity of terminals per ground bus.
d
Denotes quantity of terminals per phase and 100% neutral bus.
e
Denotes quantity of terminals per 200% neutral bus option.