Cut Sheet

29
Technical Data TD01701001E
Effective March 2017
UL low-voltage busway
Pow-R-Way III
EATON www.eaton.com
Physical data (continued)
Single-phase transformer taps (Figure 33)
Single-phase transformer taps arrangements are used for connections
to three single-phase transformers. The bus extensions do not
include drilling or lugs (see Figure 2 on page 2 for wiring
configuration designations).
Figure 33. Three single-phase transformer taps
Table 40. Single-phase transformer taps
UL 857 ampere rating Minimum dimensions in inches (mm)
Cu Al X Y
a
225 225 4.00 (101.6) 7.00 (177.8)
400 400 4.00 (101.6) 7.00 (177.8)
600 600 4.00 (101.6) 7.00 (177.8)
800 4.00 (101.6) 7.00 (177.8)
1000 4.50 (114.3) 9.75 (247.7)
1200 800 5.00 (127.0) 10.75 (273.1)
1350 1000 5.50 (139.7) 11.75 (298.5)
1600 1200 6.50 (165.1) 13.75 (349.3)
2000 1350 7.75 (196.9) 16.25 (412.8)
1600 8.50 (215.9) 17.50 (444.5)
2500 2000 10.25 (260.4) 21.25 (539.8)
3200 6.50 (165.1) 13.75 (349.3)
4000 2500 7.75 (196.9) 16.25 (412.8)
3200 8.50 (215.9) 17.50 (444.5)
5000 4000 10.25 (260.4) 21.25 (539.8)
a
Includes ground tap.
Three-phase transformer taps (Figure 34)
Three-phase transformer taps are used when making connections to
a three-phase transformer. The bus extensions do not include drilling
or lugs.
Figure 34. Three-phase transformer taps
Table 41. A minimum dimensions
Wire
designation 3W/3WH
3WG/3WHG/
3WI 4W/4WH
4WG/4WHG/4WI/
4WNG/4WNHG/4WNI
Inches 16.50 16.50 19.50 19.50
mm 419.1 419.1 495.3 495.3
Table 42. B minimum dimensions
Wire
designation 3W/3WH
3WG/3WHG/
3WI 4W/4WH
4WG/4WHG/4WI/
4WNG/4WNHG/4WNI
Inches 6.25 12.12 9.25 15.12
mm 158.8 307.8 235.0 384.0
Table 43. C minimum dimensions
Wire
designation
50% housing
ground
50% integral ground and
100% ground
Inches 3.00 6.00
mm 76.2 152.4
8.50 + y
(215.9) + y
8.50 + X
(215.9) + X
8.50 + X
(215.9) + X
8.50 + X
(215.9) + X
17.00 + 2X
(431.8) + 2X
17.00 + 2X
(431.8) + 2X
8.50 + X
(215.9) + X
8.50 + X
(215.9) + X
Pow-R-
Bridge
Ground when
Required
C Phase
or Neutral
A Phase or
Neutral
B Phase
or Neutral
Taps
C
L
C
L
Pow-R-
Bridge
C
L
Pow-R-
Bridge
C
L
Pow-R-
Bridge
C
L
Taps
C
L
Taps
C
L
6.00
(152.4)
7.50
(190.5)
N
C
B
A
G
6.00
(152.4)
C
6.00
(152.4)
6.00
(152.4)
A
Taps
B
15.00
(381.1)
(2/0)
Support Pad
(1/0)
C
C