Cut Sheet

40
Technical Data TD01701001E
Effective March 2017
UL low-voltage busway
Pow-R-Way III
EATON www.eaton.com
Plug-in device mounting (continued)
Plug-in openings are spaced every 24.00 inches (609.9 mm) starting
12.00 inches (304.8 mm) in from the centerline of each bridge joint
with a maximum of five openings per side of an individual section
of busway. Figure 61 and Figure 62 illustrate the number of plug-in
openings taken up by each style/size bus plug.
Figure 61. Fusible plug-in device mounting
Each plug-in unit uses only one plug-in opening; however, may cover
up additional plug-in openings preventing use.
Figure 62. Breaker plug-in device mounting
44.19"
P3F325 (400 A), P3F365 (400 A),
P33F236 (600 A), P3F366 (600 A),
P3F327 (800 A) and P3F367 (800 A)
(Occupies 3 Plug-in Openings)
17.00 Min.
12.00"
24.00"
24.00"
24.00"
24.00"
12.00"
8.00" Min.
18.12"
of Opening
End of Clamp
19.00"
20.75"
Can't Use
P3F321(30 A), P3F361 (30 A),
P33F361H (30 A), P3F322 (60 A),
P3F362 (60 A), P3F362H (60 A)
P3F323(100 A), P3F363(100 A)
and P3F363H (100 A)
(Occupies 1 Plug-in Opening)
P3F364H (200 A)
and P3F365H (400 A)
(Occupies 1 Plug-in Opening)
P3F324 (200 A)
and P3F364 (200 A)
(Occupies 2 Plug-in Openings)
10 ft.
Section
Shown
T
F
F
T
Can't Use
of Opening
End of Clamp
of Opening
C
L
C
L
C
L
End of Clamp
of Opening
C
L
End of Clamp
41.31"
P3B2D, P3BMD, P3BND and P3BLAP
(Occupies 2 Plug-in Openings)
17.00 MIN.
12.00"
24.00"
24.00"
24.00"
24.00"
12.00"
8.00" MIN.
16.50"
18.62"
29.75"
P3BFD
(Occupies 1 Plug-in Opening)
P3BJD
(Occupies 1 Plug-in
Opening)
P3BKD
(Occupies 2 Plug-in
Openings)
37.25"
P3BLCL
(Occupies 2 Plug-in Openings)
"T"
F
"T"
F
of Opening
C
L
of Opening
C
L
of Opening
C
L
End of Clamp
End of Clamp
End of Clamp
10 ft.
Section
Shown
of Opening
C
L
of Opening
C
L
End of Clamp
End of Clamp
Can't Use