Cut Sheet

46
Technical Data TD01701001E
Effective March 2017
UL low-voltage busway
Pow-R-Way III
EATON www.eaton.com
Plug-in device electrical data
Table 60. Circuit breakers
100% rated breakers are not available for use in bus plugs.
Contact product line for guidance.
Ampere
rating
Interrupting rating (kA symmetrical)
Breaker type240 Vac 480 Vac 600 Vac
15–60 18 14 EHD
70–100 18 14 EHD
15–60 18 14 14 FDB
70–100 18 14 14 FDB
110–150 18 14 14 FDB
15–60 65 25 18 FD
70–100 65 25 18 FD
110–150 65 25 18 FD
175–225 65 25 18 FD
15–60 100 65 25 HFD
70–100 100 65 25 HFD
110–150 100 65 25 HFD
175–225 100 65 25 HFD
15–60 200 100 35 FDC
70–100 200 100 35 FDC
110–225 200 100 35 FDC
15–100 200 150 FCL
100–225 65 ED
100–225 100 EDH
100–225 200 EDC
70–225 65 35 18 JD, JDB
250 65 35 18 JD, JDB
70–225 100 65 25 HJD
250 100 65 25 HJD
70–225 200 100 35 JDC
250 200 100 35 JDC
125–250 200 200 LCL
250–400 65 DK
100–400 65 35 25 KD, KDB
100–400 100 65 35 HKD
100–400 200 100 50 KDC
200–400 200 200 LCL
300–600 65 35 25 LD, LDB
300–600 100 65 35 HLD
300–600 200 100 50 LDC
400–800 65 50 25 MDL
400–800 100 65 35 HMDL
400–800 65 50 25 ND
400–800 100 65 35 HND
400–800 200 100 50 NDC
600–1200 65 50 25 ND
600–1200 100 65 35 HND
600–1200 200 100 50 NDC
Table 61. Integrally fused, current limiting circuit breaker
Ampere
rating
Interrupting rating (kA symmetrical)
Breaker type240 Vac 480 Vac 600 Vac
15–100 200 200 200 FB-P
125–225 200 200 200 LA-P
250–400 200 200 200 LA-P
400–600 200 200 200 NB-P
700–800 200 200 200 NB-P
Table 62. Breaker unit catalog numbering system
Figure 73. Typical circuit breaker plug-in unit
ote:N Please call Greenwood Low-voltage Busway department for help in
assigning a catalog number for a specific application.
ote:N Do not leave spaces between characters. Example: P3BFD3225N;
IBPKD3400N.
ote:N All plug-in units come fully assembled.
P3B HFD 3 015 G N
Bus style
P3B = PRWIII
IBP = PRW
BP = Old line
Breaker frame
(Ex. FD, JDC, KDB)
Three-pole only
Trip rating
(Ex. 015, 060, 150, 400)
Ground option
G = 50% internal
I = Isolated ground
(PRWIII only)
Neutral option
N = 100% neutral
N2 = 200% neutral
(PRWIII only)
ZN = Low Z
(old line only)