Cut Sheet

49
Technical Data TD01701001E
Effective March 2017
UL low-voltage busway
Pow-R-Way III
EATON www.eaton.com
Plug-in device physical data (continued)
Table 65. Standard plug-in units (continued)
Plug-in
unit
Max.
A
Max.
Vac
Dimensions in inches (mm) Standard mechanical terminal
ab
Approx.
weight
lb (kg)A B C D E F
Wire range per
phase (mm
2
)
Ground wire
range
100% neutral
wire range
Fusible plug-in units
cd
P3F321RGH
30
240
14.72
(373.9)
13.92
(353.7)
8.46
(214.8)
3.85
(97.7)
7.95
(202.0)
5.66
(143.7)
(1) #14–#2 (2.5–35) #14–1/0 #14–1/0
32
(14.5)
P3F321RGV 15.85
(402.5)
14.03
(356.3)
8.46
(214.8)
3.85
(97.7)
6.72
(170.6)
5.66
(143.7)
P3F361RGH
600
14.72
(373.9)
13.92
(353.7)
8.46
(214.8)
3.85
(97.7)
7.95
(202.0)
5.66
(143.7)
P3F361RGV 15.85
(402.5)
14.03
(356.3)
8.46
(214.8)
3.85
(97.7)
6.72
(170.6)
5.66
(143.7)
P3F322RGH
60
240
14.88
(377.9)
17.92
(455.3)
8.37
(212.5)
3.85
(97.7)
11.95
(303.6)
5.66
(143.7)
(1) #14–#2 (2.5–35) #6–3/0 #6–3/0
40
(18.1)
P3F322RGV 19.85
(504.1)
14.16
(359.6)
8.37
(212.5)
3.85
(97.7)
6.84
(173.8)
5.66
(143.7)
P3F362RGH
600
14.88
(377.9)
17.92
(455.3)
8.37
(212.5)
3.85
(97.7)
11.95
(303.6)
5.66
(143.7)
P3F362RGV 19.85
(504.1)
14.16
(359.6)
8.37
(212.5)
3.85
(97.7)
6.84
(173.8)
5.66
(143.7)
P3F323RGH
100
240
14.88
(377.9)
17.92
(455.3)
8.37
(212.5)
3.85
(97.7)
11.95
(303.6)
5.66
(143.7)
(1) #14–1/0 (2.5–50) #6–3/0 #6–3/0
40
(18.1)
P3F323RGV 19.85
(504.1)
14.16
(359.6)
8.37
(212.5)
3.85
(97.7)
6.84
(173.8)
5.66
(143.7)
P3F363RGH
600
14.88
(377.9)
17.92
(455.3)
8.37
(212.5)
3.85
(97.7)
11.95
(303.6)
5.66
(143.7)
P3F363RGV 19.85
(504.1)
14.16
(359.6)
8.37
(212.5)
3.85
(97.7)
6.84
(173.8)
5.66
(143.7)
P3F324RGH
200
240
17.42
(442.5)
21.98
(558.3)
8.52
(216.3)
3.85
(97.7)
15.44
(392.1)
6.80
(172.8)
(1) #4–300 kcmil (25–150) #6–3/0 #6–3/0
56
(25.4)
P3F324RGV 23.80
(604.5)
16.64
(422.8)
8.52
(216.3)
3.85
(97.7)
8.26
(209.8)
6.80
(172.8)
P3F364RGH
600
17.42
(442.5)
21.98
(558.3)
8.52
(216.3)
3.85
(97.7)
15.44
(392.1)
6.80
(172.8)
P3F364RGV 23.80
(604.5)
16.64
(422.8)
8.52
(216.3)
3.85
(97.7)
8.26
(209.8)
6.80
(172.8)
P3F325R
400
240
48.85
(1242.1)
21.22
(539.0)
10.07
(255.8)
4.00
(101.6)
10.69
(271.5)
10.69
(271.5)
(1) 250 kcmil–750 kcmil (120–380)
(2) 3/0–250 kcmil (95–120)
#4–350 kcmil #4–600 kcmil
77
(34.9)
P3F365R 600
P3F365HR 600
23.59
(599.2)
21.22
(539.0)
21.00
(533.4)
4.00
(101.6)
10.69
(271.5)
10.69
(271.5)
(1) #4–600 kcmil (25–300)
(2) 1/0–250 kcmil (50–120)
81
(36.7)
P3F326R
600
240
48.90
(1242.1)
26.31
(668.3)
10.59
(270.0)
4.00
(101.6)
13.16
(334.3)
13.16
(334.3)
(2) #4–600 kcmil (25–300)
(4) 1/0–250 kcmil (50–120)
#4–600 kcmil #4–600 kcmil
82
(37.1)
P3F366R 600
P3F327R
800
240
48.90
(1242.1)
26.31
(668.3)
10.59
(270.0)
4.00
(101.6)
13.16
(334.3)
13.16
(334.3)
(1) 250 kcmil–750 kcmil (120–380)
(2) 3/0–250 kcmil (95–120)
#4–600 kcmil #4–600 kcmil
108
(49.0)
P3F367R 600
a
Standard wire size terminal connections are displayed for corresponding amperage ratings. Please consult molded-case circuit breaker tech data (breaker plug-in units), Bid Manager, or product line
for other available options.
b
Consult product line for: 200% neutral terminal wire size accommodations, to deviate from standard 100% neutral terminal offering, and/or for deviation from standard ground terminal offering.
c
All plugs are manufactured to UL 857 Standards. Enclosure dimensions are for standard offerings only. Contact product line regarding implications of non-standard plugs with motor operators,
Kirk keys, neutral sensors, lighting contactors, metering, etc.
d
Alternative fuse options are available. Enclosure dimensions are not affected by fuse type.