Datasheet

03/26/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 3
Trip�block�Standard�0.3-1.2A
Part�no. PKE-XTU-1,2
Article�no. 121723
Program
Accessories Trip blocks
Setting range of overload releases I
r
A 0.3–1.2
Expansions without communication capability
Function With overload release
Rated uninterrupted current I
u
A 1.2
Motor rating
AC-3
220/230 V P kW 0.18
400 V P kW 0.37
440 V P kW 0.37
500 V P kW 0.37
690 V P kW 0.75
For use with PKE12 basic device
Motor
power
AC-3
rated
motor
current
220, 230
240 V
380, 400,
415 V
440 V 500 V 660, 690 V
P [kW] I [A) I [A) I [A) I [A) I [A)
0.06 0.37
0.09 0.54 0.31
0.12 0.72 0.41 0.37 0.33
0.18 1.04 0.6 0.54 0.48 0.35
0.25 0.8 0.76 0.7 0.5
0.37 1.1 1.02 0.9 0.7
0.55 0.9
0.75 1.1
Approbationen
UL approval Yes
CSA approval Yes
Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
NA Certification Request filed for UL and CSA
Specially designed for NA No
General
Standards IEC/EN 60947, VDE 0660, UL 508, CSA C 22.2 No. 14
Climatic proofing Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature °C
Storage °C -20 - +80
Open °C -20 - +55
Enclosed °C -20 - +40
Direction of incoming supply as required
Degree of protection
Device IP20
Main�conducting�paths
Rated impulse withstand voltage U
imp
V
AC
6000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V
AC
690
Rated uninterrupted current = rated operational current I
u
= I
e
A 1.2
Rated frequency f Hz 40 - 60
Current heat loss (3 pole at operating temperature) W 6
Motor switching capacity kA
rms
AC-3 (up to 690 V) A 1
Trip�blocks

Summary of content (3 pages)