Datasheet

03/21/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 8
Mounting position
Direction of incoming supply as required
Degree of protection
Device IP20
Terminations IP00
Protection against direct contact Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC
60068-2-27
g 25
Altitude m 2000
Terminal capacity screw terminals
mm
2
Solid
mm
2
1 x (1 - 6)
2 x (1 - 6)
Flexible with ferrule to DIN 46228
mm
2
1 x (1 - 6)
2 x (1 - 6)
Solid or stranded AWG 18 - 10
Terminal capacity springloaded terminals
Solid
mm
2
1 x (1…2.5)
2 x (1…2.5)
Flexible with ferrule to DIN 46228
mm
2
1 x (1…2.5)
2 x (1…2.5)
Solid or stranded AWG 18…14
Specified tightening torque for terminal screws
Main cable Nm 1.7
Control circuit cables Nm 1
Main�conducting�paths
Rated impulse withstand voltage U
imp
V
AC
6000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V
AC
690
Rated uninterrupted current = rated operational current I
u
= I
e
A 32 or current setting of the overcurrent release
Rated frequency f Hz 40 - 60
Rated frequency Hz 40 - 60
Current heat loss (3 pole at operating temperature) W 6
Lifespan, mechanical Operations x
10
6
0.1
Lifespan, electrical (AC-3 at 400 V) Operations x
10
6
0.1
Maximum operating frequency Ops./
h
Max. operating frequency Ops/
h
40
Short-circuit rating
AC
→Engineering
DC
Short-circuit rating kA 60
Short-circuit rating 60 (up to PKZM0-16)
40 (PKZM0-20 to PKZM0-32)
Motor switching capacity kA
rms
AC-3 (up to 690 V) A 32
DC-5 (up to 250 V) A 25 (3 contacts in series)
Trip�blocks
Temperature compensation
to IEC/EN 60947, VDE 0660 °C - 5 … 40
Operating range °C - 25 … 55