Datasheet

03/22/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 6
Motor-prot.circuit�breaker�PKZM01-1,6
Part�no. PKZM01-1,6
Article�no. 278480
Program
Contact sequence
220 - 240 V
AC-3
220 V
230 V
240 V
P kW 0.25
380 V
400 V
415 V
P kW 0.55
440 V P kW 0.55
Rated uninterrupted current I
u
A 1.6
Setting�range
Overload releases I
r
A 1 - 1.6
Short-circuit releases
max. I
rm
A 22
Notes
Accessories Page
3 Standard auxiliary contact →072896
5 Trip-indicating auxiliary contact →072898
6 Shunt release, undervoltage release →073187
Single-phasing sensitivity according to IEC/EN 60947‐4‐1, VDE0660 Part102.
Can be snap-fitted to IEC/EN 60715 top-hat rail with 7.5 or 15mm height
Approbationen
UL approval Yes
CSA approval Yes
Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
UL File No. E36332
UL CCN NLRV
CSA File No. 12528
CSA Class No. 3211-05
NA Certification UL listed, CSA certified
Specially designed for NA No
Suitable for Branch circuit: Manual type E if used with terminal, or suitable for group installations
General
Standards IEC/EN 60947, VDE 0660
Climatic proofing Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature °C
Storage °C - 25 - 80
Open °C - 25 - 55
Enclosed °C - 25 - 40
Mounting position

Summary of content (6 pages)