Datasheet

03/22/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 6
Direction of incoming supply as required
Degree of protection
Device IP20
Terminations IP00
Protection against direct contact Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC
60068-2-27
g 25
Altitude m 2000
Terminal capacity screw terminals
mm
2
Solid
mm
2
1 x (1 - 6)
2 x (1 - 6)
Flexible with ferrule to DIN 46228
mm
2
1 x (1 - 6)
2 x (1 - 6)
Solid or stranded AWG 18 - 10
Specified tightening torque for terminal screws
Main cable Nm 1.7
Control circuit cables Nm 1
Main�conducting�paths
Rated impulse withstand voltage U
imp
V
AC
6000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V
AC
690
Rated uninterrupted current = rated operational current I
u
= I
e
A 16 or current setting of the overcurrent release
Rated frequency f Hz 40 - 60
Rated frequency Hz 40 - 60
Current heat loss (3 pole at operating temperature) W 6
Lifespan, mechanical Operations x
10
6
0.05
Lifespan, electrical (AC-3 at 400 V) Operations x
10
6
0.05
Maximum operating frequency Ops./
h
Max. operating frequency Ops/
h
25
Short-circuit rating
AC
→Engineering
DC
Short-circuit rating kA 60
Short-circuit rating 60
Motor switching capacity kA
rms
AC-3 (up to 690 V) A 16
DC-5 (up to 250 V) A 16 (3 contacts in series)
Trip�blocks
Temperature compensation
to IEC/EN 60947, VDE 0660 °C - 5 … 40
Operating range °C - 25 … 55
Temperature compensation residual error for T > 40 °C
0.25%/K
Setting range of overload releases x I
u
0.6 - 1
Short-circuit release fixed x I
u
14
Fixed short-circuit release Basic device 14 x I
u
Short-circuit release tolerance ± 20%
Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
Technical�data�according�to�ETIM�4.0
Rated operation power at AC-3, 400 V kWh 0.55
With integrated auxiliary switch No