® Powerware 5125 Tower User’s Guide 1000–2200 VA www.powerware.
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: S Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 950 Second Edition, Amendments A1, A2, A3, and A4 S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC
Class A EMC Statements (1000–1500 VA Models) FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Special Symbols The following are examples of symbols used on the UPS to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions. RJ-45 RECEPTACLE - For 230V units only: this receptacle provides network interface connections.
TABLE OF CONTENTS 1 Powerware 5125 – One of the Best! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents 7 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Audible Alarms and UPS Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Silencing an Audible Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 1 POWERWARE 5125 – ONE OF THE BEST! The PowerwareR 5125 uninterruptible power system (UPS) protects your sensitive electronic equipment from basic power problems such as power failures, power sags, power surges, brownouts, and line noise. Power outages can occur when you least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware — causing hours of lost productivity and expensive repairs.
Powerware 5125 – ONE OF THE BEST! Providing outstanding performance and reliability, the Powerware 5125’s unique benefits include the following: S S S S S S S S S S 2 Advanced Battery Management Plus (ABM Plust) doubles battery service life, optimizes recharge time, and provides a warning before the end of useful battery life. Buck and Double Boost regulation ensures consistent voltage to your load by correcting voltage fluctuations without using battery power.
CHAPTER 2 SAFETY WARNINGS Read the following precautions before you install the UPS. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. DANGER This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
Safety Warnings CAUTION S Batteries can present a risk of electrical shock or burn from high short-circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries. S Proper disposal of batteries is required. Refer to your local codes for disposal requirements. S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Safety Warnings ADVARSEL S Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj kortslutningsspænding. De korrekte forholdsregler bør overholdes. S Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer. S Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved åben ild.
Safety Warnings OPGELET S Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op. S De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. S Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.
Safety Warnings VARO S Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään oikosulkuun. Noudata asianmukaisia ohjeita. S Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. S Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Consignes de sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES DANGER! Cet onduleur contient des TENSIONS MORTELLES.
Safety Warnings ATTENTION! S Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts-circuits de haute intensité. Prendre les précautions nécessaires. S Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. S Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser. Sicherheitswarnungen WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN.
Safety Warnings VORSICHT! S Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind unbedingt zu beachten. S Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen Bestimmungen zu beachten. S Batterien niemals verbrennen, da sie explodieren können.
Safety Warnings S * .;1 " . / > . 5 1/"1 = 5. / ! 3 . 5= " / / . . 3 / ! . = / " . ! 5 E=C F6 S S S 1 . " 3" ! . G 5. 8 :. H .84 4 ; 43 " 1 / 4> 1 1 : ) " 5 . 5 ; 5 / 4> $ . 4 1 ;1 4= ! " .
Safety Warnings S Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti contaminanti conduttivi. La temperatura ambiente non deve superare i 40°C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max).
Safety Warnings S Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere total lekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser. FORSIKTIG S Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy kortslutningsstrøm. Følg instruksene. S Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier.
Safety Warnings PERIGO S As baterias podem apresentar o risco de choque elétrico, ou queimaduras provenientes de alta corrente de curto-circuito. Observe as instruções adequadas. S Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do local para maiores informações sobre os regulamentos de descarte de produtos. S Nunca jogue as baterias no fogo, porque há risco de explosão.
Safety Warnings S Для обеспечения соблюдения требований международных стандартов и требований к разводке электрических цепей, суммарная величина тока утечки на землю всего оборудования, подключенного к выходу ИБП, не должна превышать 1,5 миллиампера. ОСТОРОЖНО S Аккумуляторы могут вызвать опасность поражения электрическим током или ожога от тока короткого замыкания. Соблюдайте соответствующие меры предосторожности. S Необходимо соблюдать правила утилизации аккумуляторов.
Safety Warnings S Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un lugar cubierto, con temperatura y humedad controladas, libre de contaminantes conductores. La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o con humedad excesiva (95% máximo).
Safety Warnings S Minska risken för brand eller elektriska stötar genom att installera denna UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).
CHAPTER 3 INSTALLATION This section explains: S Equipment inspection S UPS installation S UPS rear panels Inspecting the Equipment If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
Installation Communication Port EBM Battery Connector EBM Cable UPS Battery Connector Power Cord Output Receptacles Figure 2. Typical Installation with Two EBMs 4. If you are installing power management software, connect your computer to the UPS communication port using the supplied communication cable. 5. On 208V/230V models, plug the detachable UPS power cord into the input connector on the UPS rear panel. 6. Plug the UPS power cord into a power outlet.
Installation µ 8. Press and hold the On button until you hear the UPS beep indicator stops flashing (approximately one second). The and the bar graph indicators display the percentage of load being applied to the UPS. The UPS is now in Normal mode and supplying power to your equipment. NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 24 hours after installation or long-term storage.
Installation UPS Rear Panels This section shows the rear panels of the Powerware 5125 models. Communication Port X-Slot Network Transient Protector Fan Six 5-15R Receptacles Battery Connector 6-ft Power Cord with 5-15 Plug Figure 3. PW5125 1000 and PW5125 1500 Rear Panel Communication Port X-Slot Network Transient Protector Fan Six 5-15R Receptacles Battery Connector Two 5-20R Receptacles 6-ft Power Cord with 5-20 Plug Figure 4.
Installation Communication Port X-Slot Network Transient Protector Fan Six 10A, IEC 320-C13 Receptacles 10A, IEC-320 Input Connector Battery Connector Figure 5. PW5125 1000i and PW5125 1500i Rear Panel Communication Port X-Slot Network Transient Protector Fan Nine 10A, IEC 320-C13 Receptacles Battery Connector 10A, IEC-320 Input Connector Figure 6. PW5125 2200i Rear Panel Powerware® 5125 Tower (1000–2200 VA) User’s Guide S Rev B www.powerware.
Installation Communication Port X-Slot Network Transient Protector Fan Six 5-15R Receptacles Battery Connector 6-ft Power Cord with 5-15 Plug Figure 7. PW5125 1000j Rear Panel Communication Port X-Slot Network Transient Protector Fan Six 5-15R Receptacles Battery Connector 6-ft Power Cord with 5-20 Plug Figure 8. PW5125 1500j Rear Panel 22 Powerware® 5125 Tower (1000–2200 VA) User’s Guide S Rev B www.powerware.
Installation Communication Port X-Slot Network Transient Protector Fan Six 5-15R Receptacles Battery Connector Two 5-20R Receptacles 6-ft Power Cord with L5-30 Plug Figure 9. PW5125 2200j Rear Panel Communication Port X-Slot Network Transient Protector Fan Nine 10A, IEC 320-C13 Receptacles Battery Connector 15A, IEC-320 Input Connector Figure 10. PW5125 2200b Rear Panel Powerware® 5125 Tower (1000–2200 VA) User’s Guide S Rev B www.powerware.
Installation 24 Powerware® 5125 Tower (1000–2200 VA) User’s Guide S Rev B www.powerware.
CHAPTER 4 OPERATION This section describes: S Operating modes S Turning the UPS on and off S Starting the UPS on battery S Initiating the self-test Operating Modes Powerware 5125’s front panel indicates the UPS status through the UPS indicators. Figure 11 shows the UPS front panel indicators and controls.
Operation Normal Mode µ During Normal mode, the indicator illuminates and the front panel displays the percentage of UPS load capacity being used by the protected equipment (see Figure 12). The UPS monitors and charges the batteries as needed and provides power protection to your equipment. >100% 76–100% 51–75% 26–50% 0–25% Figure 12. Load Level Indicators When all of the bar graph indicators and the indicator are illuminated, power requirements exceed UPS capacity; see page 45 for more information.
Operation Battery Mode When the UPS is operating during a power outage, the alarm beeps once every four seconds and the + -- indicator illuminates. When the utility power returns, the UPS switches to Normal mode operation while the battery recharges. indicator If battery capacity becomes low while in Battery mode, the flashes and the alarm beeps twice every two seconds. Immediately complete and save your work to prevent data loss and similar difficulties.
Operation Turning the UPS Off µ To turn off the UPS, press and hold the Off button until the long indicator begins to beep ceases (approximately five seconds). The flash and the UPS remains in Standby mode until you unplug the UPS from the power outlet. Initiating the Self-Test NOTE The batteries must be fully charged to perform the self-test. Press and hold the button for three seconds to initiate the self-test. During the test, individual indicators illuminate as various parts of the UPS are checked.
CHAPTER 5 ADDITIONAL UPS FEATURES This section describes: S X-Slot modules S Network Transient Protector S Load segments X-Slot Modules X-Slot modules allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 5125 is factory-installed with a Single-Port module and is compatible with any X-Slot module, including: S Multi-Server Module - has six serial communication ports that can communicate with UPSs, terminals, computers, and modems.
Additional UPS Features Single-Port Module The Powerware 5125 is factory-installed with a Single-Port Module. To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable. When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment.
Additional UPS Features Network Transient Protector The Network Transient Protector, shown in Figure 16, is located on the rear panel and has jacks labeled IN and OUT. This feature accommodates a single RJ-45 (10BaseT) network connector. Low voltage models can also accommodate an RJ-11 telephone connector that provides protection for modems, fax machines, or other telecommunications equipment.
Additional UPS Features Load Segments Load segments are sets of receptacles that can be controlled by power management software, providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep key pieces of equipment running while you turn off other equipment. This feature allows you to save battery power. See your power management software manual for details. NOTE If the power management software is not used, the individual load segments cannot be controlled.
CHAPTER 6 UPS MAINTENANCE This section explains how to: S Care for the UPS and batteries S Replace the batteries S Test new batteries S Recycle used batteries UPS and Battery Care For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).
UPS Maintenance Replacing Batteries NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode. With the hot-swappable battery feature, UPS batteries can be replaced easily without turning the UPS off or disconnecting the load. If you prefer to remove input power to change the battery: 1) Press and hold the Off button until the long beep ceases (approximately five seconds), then unplug the UPS; 2) Wait 60 seconds while the internal processor shuts down before you disconnect the battery.
UPS Maintenance How to Replace Internal Batteries CAUTION Pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it out of the UPS. Use the following procedure to replace internal batteries: 1. Remove the UPS front panel by pulling the top. 2. Slide up and remove the metal battery cover. 1000 VA Powerware® 5125 Tower (1000–2200 VA) User’s Guide S Rev B www.powerware.
UPS Maintenance 3. 1000 VA units. Disconnect the red battery cable on the front of the battery. Pull the battery out onto a flat, stable surface. Disconnect the black battery cable on the rear of the battery, then on the front of the battery. Disconnect the red battery cable on the rear of the battery. See “Recycling the Used Battery” on page 38 for proper disposal. 1000 VA 36 Powerware® 5125 Tower (1000–2200 VA) User’s Guide S Rev B www.powerware.
UPS Maintenance 4. 1500 and 2200 VA units. Pull the battery out onto a flat, stable surface. Press on the black tab on the battery cable connector to disconnect the battery. See “Recycling the Used Battery” on page 38 for proper disposal. 1500 and 2200 VA 5. Install the new batteries in the reverse order of removal. 6. Reinstall the metal battery cover removed in Step 2. Replace the front panel. Testing New Batteries Press and hold the button for three seconds to initiate a self-test.
UPS Maintenance Recycling the Used Battery Contact your local recycling or hazardous waste center for information on proper disposal of the used battery. WARNING S Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
CHAPTER 7 SPECIFICATIONS This section provides the following specifications for the Powerware 5125 models: S Electrical input and output S Weights and dimensions S Environmental and safety S Battery Table 2.
Specifications Table 4.
Specifications Table 6.
Specifications Table 8. Battery Run Times (in Minutes at Full/Half Load) Model Internal UPS Batteries 1 EBM 2 EBMs 3 EBMs 4 EBMs 1000 VA 5/14 25/60 55/170 83/199 109/228 1500 VA 6/17 33/79 63/146 92/174 120/201 2200 VA 5/14 26/60 55/170 81/198 106/224 N OTE Battery times are approximate and vary depending on the load configuration and battery charge. 42 Powerware® 5125 Tower (1000–2200 VA) User’s Guide S Rev B www.powerware.
CHAPTER 8 TROUBLESHOOTING This section explains: S UPS alarms and conditions How to silence an alarm S Service and support S Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems. Use Table 9 to determine and resolve the UPS alarms and conditions. Indicator Legend Unlit Green Red On Button Flashing Off Button Test/Alarm Reset Button General Alarm On Battery Battery Service Site Wiring Fault Power On Figure 20.
Troubleshooting Silencing an Audible Alarm To silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing. The alarm does not silence if there is a low battery condition. Table 9. Troubleshooting Guide Alarm or Condition µ Possible Cause Action The indicator is not on; the UPS does not start. The power cord is not connected correctly. Check the power cord connections. µ The wall outlet is faulty.
Troubleshooting Alarm or Condition 1 beep every 5 seconds. Possible Cause Action The UPS is running on battery power because the input voltage is too high or too low. Correct the input voltage, if possible. The UPS continues to operate on battery until the condition is corrected or the battery is completely discharged. If the condition persists, the input voltage in your area may differ from the UPS nominal. The utility line voltage and frequency are out of specification.
Troubleshooting Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.