® powerware 9 Prestige Series User’s Guide 4500/6000 VA www.powerware.
FCC Statement The PowerwareR 9 Prestige Series UPS configurations vary. Some configurations may or may not be classified by the Federal Communications Commission (FCC). If your Prestige unit is classified by these standards, the corresponding information applies: Class A NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
UPS QUICK INSTALLATION CAUTION Read the safety instructions beginning on page 5 before installing the UPS.
UPS Quick Installation 5 6 7
UPS with Optional PPDM Quick Installation UPS WITH OPTIONAL PPDM QUICK INSTALLATION CAUTION Read the safety instructions beginning on page 5 before installing the UPS.
UPS with Optional PPDM Quick Installation 5 6 7 9 8
TABLE OF CONTENTS 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 UPS Model and Battery Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Load Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Times for the Prestige 6000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents 5 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Initial Communications Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Front Panel Communications Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS Serial Communications Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 1 INTRODUCTION Congratulations on the purchase of your PowerwareR 9 Prestige Series uninterruptible power system (UPS). The Prestige UPS meets the toughest measures of superior design and manufacturing, including ISO 9001. You now own the most reliable power protection available. The Prestige 6000 provides a steady, well-regulated power supply for your computing and communications equipment, while protecting it from the frequent irregularities that are inherent in commercially available power.
Introduction UPS Model and Battery Configurations This UPS is designed to work with single-phase, three-wire, AC power sources. There are two important considerations when selecting the UPS model and battery configuration to properly safeguard your equipment: S Load requirements S Battery times Load Requirements The load is the equipment to be protected by the UPS. Select the UPS model that meets the power consumption requirements of the load in volt-amperes (VA).
Introduction 3. Add all of the resultant VA ratings together to obtain the total load requirements of the equipment to be protected (see Figure 2). If the load consists of the power-factor corrected supplies, it is recommended to use total watts for the load requirements. 3 COMPUTERS 3 MONITORS EXTERNAL MODEM 300 WATTS EACH 2 AMPS EACH 3 x 300 WATTS X 1.4 = 1260 VA 3 x 2 AMPS x 240V = 1440 VA 50 VA 50 VA 1260 VA + 1440 VA + 50 VA = 2750 VA (Total Load Requirements) Figure 2.
Introduction Special Symbols The following common symbols may be found on the UPS: LOAD ON - Press the button with this symbol to energize the output receptacles (Output On). LOAD OFF - Press the button with this symbol to de-energize the output receptacles (Output Off). SAFETY EARTHING TERMINAL - Indicates the primary safety ground. RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
CHAPTER 2 SAFETY WARNINGS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation of the UPS. Please read all instructions before operating the equipment and save this manual for future reference. DANGER This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
Safety Warnings S Please note that the output sockets on the UPS are electrically live whenever the UPS Output On button is pressed, even if the input cord is disconnected. S To reduce the risk of fire, connect the UPS and PPDM only to circuits provided with 30 amperes maximum branch-circuit overcurrent protection. S For PPDM systems with hardwired outputs, overcurrent protection for the output AC circuit(s) is to be provided by others.
Safety Warnings S Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til. S Stikkontakten må højst være 2 meter fra udstyret og tilgængelig for brugeren. UPS’ens afbryderkontakt isolerer ikke elektrisk de indvendige dele. Træk derfor stikket ud af kontakten, hvis enheden er slukket i lang tid ad gangen.
Safety Warnings S Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. S Nooit batterijen openen of beschadigen. Vrijkomend elektrolyt is schadelijk voor de huid en ogen, en kan uiterst giftig zijn. S Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40_C niet overschrijden.
Safety Warnings Tärkeitä turvaohjeita TÄRKEITÄ TURVAOHJEITA - SUOMI SÄILYTÄ NÄMÄ OHJEET TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA VAARA Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA. VARO S Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään oikosulkuun. Noudata asianmukaisia ohjeita. S Akusto täytyy hävittää säädösten mukaisella tavalla.
Safety Warnings S Tämän laitteen mukana ei toimiteta lähdön ylivirtasuojausta kiinteän asennuksen ohitusjärjestelmissä. S Tämän laitteen mukana ei toimiteta lähdön johdonsuojakatkaisijoita jakeluja varten kiinteän asennuksen ohitusjärjestelmissä. Consignes de sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES DANGER! Cet onduleur contient des TENSIONS MORTELLES.
Safety Warnings S La prise secteur doit se trouver à moins de 2 m du matériel et être accessible à l’utilisateur. L’interrupteur de ON/OFF (marche/arrêt) de l’onduleur n’assure pas l’isolation électrique des pièces internes. Débrancher le cordon d’alimentation de la prise secteur en cas de déconnexion de l’appareil pendant une période prolongée.
Safety Warnings S Batterien nie öffnen oder anderweitig beschädigen. Der darin enthaltene Elektrolyt wirkt ätzend auf Haut und Augen. Es besteht Vergiftungsgefahr! S Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40_C nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max.
Safety Warnings !" # $ %& ' ( ) #% *( ' $ +$(, )% $% (%-%( , % %& # $ ' #$ %( %$( ,%' %( $ - S S S S S S S .
Safety Warnings S S "F " 8 3 " / ! 2 H / 0 / " 6 / 8 IJKILL 8 / 4 6 .
Safety Warnings S questo gruppo statico di continuità contiene una fonte di energia autonoma (le batterie). Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuità non è collegato con una fonte di alimentazione a corrente alternata. S non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. S mai aprire nè mutilare le batterie poichè l’elettrolita da esse rilasciato è nocivo alla cute e agli occhi e può essere altamente tossico.
Safety Warnings Viktig Sikkerhetsinformasion FARLIG Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅ NOEN AV DELENE i UPS’en. FORSIKTIG S Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy kortslutningsstrøm. Følg instruksene. S Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier.
Safety Warnings Regulamentos de Segurança INSTRUÇÕES DE SEGURANÇA IMPORTANTES GUARDE ESTAS INSTRUÇÕES ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA IMPORTANTES CUIDADO A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
Safety Warnings S Para sistemas Bypass com saídas conectadas, a proteção de sobrecarga para circuitos de saída de corrente alternada deve ser fornecida por outros. S Para sistemas Bypass com saídas conectadas, interruptores de desconexão devidamente qualificados para circuitos de saída de corrente alternada devem ser fornecidos por outros.
Safety Warnings S Для снижения опасности пожара или поражения электрическим током устанавливайте ИБП в закрытом помещении с контролируемыми температурой и влажностью, в котором отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40°С. Не эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%). S Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки при включенном ИБП.
Safety Warnings Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES PELIGRO Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.
Safety Warnings S Tenga en cuenta que los receptáculos de salida del SIE tienen corriente eléctrica siempre que se oprime el botón pulsador de conexión de salida del SIE (Output ON), aun cuando el cable de entrada esté desconectado. S Para reducir el riesgo de incendio, conecte el SIE y el bypass solamente a circuitos con protección por sobreintensidad de las ramas de un máximo de 30 A.
Safety Warnings S Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort säkerhetsjordningen från både UPS-enheten och den anslutna utrustningen. S Vägguttaget får vara högst 2 meter från utrustningen och måste vara inom räckhåll för användaren. UPS-enhetens strömbrytare isolerar inte elektriskt de interna delarna. Vid längre avstängning bör nätsladden dras ur vägguttaget.
CHAPTER 3 INSTALLATION The following sections describe UPS storage requirements and the installation and startup of the UPS. Unpacking and Inspection Carefully unpack the UPS and any other cabinets, making sure to retain the packaging materials. Examine each unit carefully for any signs of damage and immediately notify your distributor if damage is present. UPS and Battery Cabinet Storage If you plan to store the UPS or battery cabinets prior to use, store them in a cool, dry environment.
Installation Selecting an Installation Option You are now ready to install the Prestige 6000. Use the following flow chart to decide which installation option is right for you. Do you have an optional PPDM? Yes See “UPS with Optional PPDM Installation” on page 37. No Is the PPU hardwired? Yes See “UPS Hardwired Installation” on page 29. No See “UPS Plug/Receptacle Installation” below.
Installation NOTE Do not connect more than six standard battery cabinets to the PPU. For extended battery run times, contact your local distributor for additional battery cabinets. Do not place more than six cabinets in one stack (the PPU is equal to two cabinets). Battery Cabinets Air Vents PPU PPU Battery Cabinets Figure 3. Cabinet Setup NOTE You can install additional battery cabinets while the UPS is operating, but confirm the UPS is not in Battery mode (see page 51). 2.
Installation Battery Connector Guard Battery Cabinet Battery Connector Battery Circuit Breaker Battery Connector Battery Cabinet Breaker Tie Serial Port Input Plug Input Breaker PPU Output Receptacle Battery Connector Voltage Selector Switch REPO Receptacle Figure 4. UPS with Plug/Receptacle PPU Rear Panel 26 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.
Installation 5. If additional battery cabinets are to be used, plug the battery cord of the second cabinet into the battery connector of the first cabinet after pivoting the battery connector guard out of the way. Follow this procedure for each additional battery cabinet. 6. Remove the breaker tie from the circuit breaker on all battery cabinets. 7. Select the correct UPS output voltage. Using a screwdriver, turn the switch to the corresponding position of the output voltage required (see Figure 5).
Installation 9. If you are using a Remote Emergency Power-Off (REPO) switch, follow the instructions in the following section, “REPO Installation.” 10. Start the UPS according to the “UPS Startup” procedure on page 36. REPO Installation WARNING Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation. The REPO switch is a customer-supplied switch that can disconnect UPS output voltage from your protected equipment.
Installation Mounting Holes Plug/Receptacle PPU Connector Access Hole for Conduit Three Foot Cord Terminal Block Figure 6. Optional REPO Cord Junction Box Optional REPO Cord Junction Box Connections Wire Function REPO Terminal Position L1 TB1-4 L2 TB1-5 Ground TB1-6 Terminal Wire Size Rating Suggested Wire Size 12 - 22 AWG (4 - 0 mm2) 18 AWG ((0.75 mm2) N OTE The REPO function activates when L1 and L2 are shorted together.
Installation Battery Cabinets Air Vents PPU PPU Battery Cabinets Figure 7. Cabinet Setup NOTE You can install additional battery cabinets while the UPS is operating, but confirm the UPS is not in Battery mode (see page 51). 2. Verify the input breaker on the PPU rear panel is in the OFF (O) position (see Figure 8). 3. Verify the circuit breaker on all battery cabinets is in the OFF (O) position. 30 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.
Installation Panel Cover Screws Serial Port Battery Battery Connector Guard Connector REPO Cable Entry Input Cable Entry Input Breaker Panel Cover Screws Output Cable Entry Battery Connector PPU Voltage Selector Switch Battery Breaker Tie Circuit Breaker Battery Cabinets Figure 8. UPS with Hardwired PPU Rear Panel 4. Select the correct UPS output voltage. Using a screwdriver, turn the switch to the corresponding position of the output voltage required (see Figure 9).
Installation Voltage Selector Switch Figure 9. Voltage Selector Switch 5. Remove the four screws on the PPU rear panel with a Phillips screwdriver and remove the PPU back panel cover. Input Cable Connections (TB1-1 to TB1-3) REPO Connections (TB1-4 to TB1-6) Battery Connector Output Cable Connections (TB2) Figure 10. Hardwired PPU with Rear Panel Cover Removed 32 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.
Installation 6. Hardwire the input (TB1-1 through TB1-3) and output terminations (TB2) for the PPU. See the following hardwired terminations table for specifications. See Figure 11 for a detailed view of the terminal blocks.
Installation Input Connection Output Connection TB1 TB2 Input Connections REPO Connections Ground Line 2/Neutral Line 1 Ground Line 1 Line 2/Neutral REPO Line 1 REPO Line 2 REPO Ground Figure 11. Hardwired PPU Terminal Blocks 7. Determine your equipment’s grounding requirements according to your local electrical code. 8. As part of the branch circuit that supplies this unit, install an insulated grounding conductor.
Installation 9. If you are using a REPO switch, hardwire the terminal block TB1, positions TB1-4 through TB1-6. See the hardwired termination table on page 33 for proper connections. Figure 10 on page 32 shows the connection locations and Figure 11 on page 34 shows a detailed view of the terminal blocks. The REPO switch is a customer-supplied switch that can disconnect the UPS output voltage from your protected equipment. The REPO function activates when the L1 and L2 wires are shorted together.
Installation UPS Startup To start up the UPS: 1. Verify the input breaker on the PPU rear panel is in the OFF (O) position (see Figure 4 on page 26). 2. Confirm the correct UPS output voltage is selected (see Step 7 on page 27). 3. Turn on the equipment that is connected to the UPS. 4. If your PPU is a hardwired unit, supply utility power to the UPS and skip to Step 7. 5. If your PPU is a plug/receptacle unit, plug the UPS power supply cord into the power input connector on the PPU rear panel. 6.
Installation µ The indicator remains lit and the Self Test indicator turns on. The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. See “Normal Mode” on page 50 for more information. 10. If you connected a REPO switch to the UPS, test the switch while the UPS is operating to ensure proper operation. Press the REPO switch. The UPS shuts down and stops providing power to the equipment.
Installation Air Vents Battery Cabinets PPU PPDM Figure 12. UPS with PPDM NOTE You can install additional battery cabinets while the UPS is operating, but confirm the UPS is not in Battery mode (see page 51). 2. Verify the Bypass switch on the PPDM rear panel is in the NORMAL position (see Figure 13). 3. Verify the circuit breaker on all battery cabinets is in the OFF (O) position (see Figure 14). 38 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.
Installation L5-30R, L6-20R, L6-30R, or L14-30R Receptacles (Model Dependent) Power Cords To PPU Utility Input To PPDM (Cord Provided) Circuit Protectors for Locking Receptacles (Model Dependent) Input Breaker Bypass Switch 5-15R Circuit Protectors 5-15R Receptacles Figure 13. PPDM Plug/Receptacle Unit Rear Panel Connections Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.
Installation Input Breaker Input Plug Output Receptacle PPU Battery Connector REPO Receptacle Voltage Selector Switch Battery Connector Guard Serial Port Circuit Breaker Breaker Tie Battery Connector Battery Cord Battery Cabinets Figure 14. UPS with Plug/Receptacle PPU Rear Panel 40 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.
Installation 4.
Installation Voltage Selector Switch Figure 15. Voltage Selector Switch 5. Plug the input and output power cords of the PPDM into the input and output power connectors on the PPU rear panel (see Figure 13 and Figure 14). Figure 24 on page 55 shows the PPDM and PPU rear panel connections. 6. For a plug/receptacle PPDM, continue to Step 7. For a hardwired PPDM, skip to Step 8. 7. The equipment to be protected by the UPS should be powered off.
Installation 8. Remove the screws on the PPDM rear panel with a Phillips screwdriver and remove the PPDM back panel cover. WARNING Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation. Power Cords To PPU Input Cable Connections (TB1) Input Conduit Entry Bypass Switch Output Cable Connections (TB2) Output Conduit Entry Input Breaker Figure 16.
Installation 9. Hardwire the input (TB1) and output terminations (TB2) for the PPDM. See the following hardwired terminations table for specifications. See Figure 17 for a detailed view of the terminal blocks.
Installation Input Connection TB1 Output Connection TB2 Neutral Bonding Jumper Ground Neutral TB2-3 TB2-2 TB2-1 Line 1 Line 2/Neutral Ground Figure 17. Hardwired PPDM Terminal Blocks NOTE Model 240: 120/240E only. The neutral bonding jumper on TB2 of the PPDM grounds an output phase and may need to be removed. Refer to your local electrical code requirements. 10. Determine your equipment’s grounding requirements according to your local electrical code.
Installation 11. As part of the branch circuit that supplies this unit, install an insulated grounding conductor. Use the following specifications for the grounding conductor that connects to input ground terminal TB1-3.
Installation UPS with PPDM Startup To start up the UPS: 1. Verify the PPDM input breaker is in the OFF (O) position (see Figure 13 on page 39). 2. Confirm the correct UPS output voltage is selected (see Step 4 on page 41). 3. Turn on the equipment that is connected to the UPS. 4. Confirm the Bypass switch on the PPDM rear panel is in the NORMAL position (see Figure 13 on page 39). 5. If your PPDM is a hardwired unit, supply utility power to the UPS and skip to Step 8. 6.
Installation 12. Press and hold the Output On button until you hear the UPS beep (approximately one second). µ The indicator remains lit and the Self Test indicator turns on. The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. See “Normal Mode” on page 50 for more information. 13. If you connected a REPO switch to the UPS, test the switch while the UPS is operating to ensure proper operation. Press the REPO switch.
CHAPTER 4 UPS OPERATION This chapter covers the operation of the UPS including front panel functions, operating modes, using the Battery Start feature, shutting down the UPS, and using the PowerPass Distribution Module. UPS Front Panel The UPS front panel has three distinct functions: S Displays the UPS operational mode (Normal, Bypass, or Battery). S Displays any alarm conditions present during operation (the indicators flash).
UPS Operation Operating Modes After you install and apply power to the UPS, the UPS filters and regulates incoming AC power, eliminating noise and voltage spikes, and provides consistent power to your equipment (see Figure 19). While power is applied to the UPS, the maintenance-free battery is automatically kept in a fully-charged condition.
UPS Operation µ Bypass Mode The indicator and the indicator illuminate simultaneously, indicating Bypass mode (see Figure 21). When the UPS is in Bypass mode, the load is powered by utility power. However, utility power continues to be passively filtered by the UPS. OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST LOAD ON UNIT ON BYPASS Figure 21.
UPS Operation When shutdown is imminent, the Self Test indicator flashes. These warnings are approximate, and the actual time to shutdown may vary significantly. Once these warnings are indicated, immediately complete and save your work to prevent data loss and similar difficulties. When utility power is restored after the UPS shuts down, the UPS automatically connects to the load when the startup is complete.
UPS Operation UPS Shutdown Performing a UPS shutdown turns off the power to your protected equipment. Confirm the equipment is prepared for a power-off before shutting down the UPS. NOTE Do not perform a UPS shutdown if you want to use the Maintenance Bypass feature on the optional PPDM (see “Using the PPDM” on page 54). To perform a UPS shutdown: 1. Press and hold the Output Off button until the long beep ceases (approximately three seconds).
UPS Operation Using the PPDM The PPDM provides continuous online power for your equipment. With the PPDM, you can replace or upgrade the PPU without losing power to your equipment. Figure 23 shows the operation of the UPS with the PPDM. Utility Power In PPU Out PPDM Battery UPS Load Battery Figure 23. UPS and PPDM Block Diagram Using Maintenance Bypass Use the following procedure to transfer the critical load to Maintenance Bypass (AC Line operation) and remove the PPU: 1.
UPS Operation 4. Remove the cord connections to the back of the PPU. 5. Switch the circuit breaker on all battery cabinets to the OFF (O) position. 6. Disconnect the battery connector on the PPU rear panel. 7. Remove the PPU.
UPS Operation Use the following procedure to reinstall the PPU and transfer the critical load from Maintenance Bypass (AC Line operation) to the PPU: 1. Reconnect the battery cabinet to the battery connector on the PPU rear panel. 2. Switch the circuit breaker on all battery cabinets to the ON ( | ) position. 3.
UPS Operation Voltage Selector Switch Figure 25. Voltage Selector Switch 4. Plug the input and output cords of the PPDM into the power connectors on the PPU as shown in Figure 24 on page 55. 5. Switch the PPU input breaker to the ON ( | ) position. After a short delay (approximately three seconds), the UPS front panel indicators turn on and cycle through several times. and indicators remain lit for several seconds (UPS The in Bypass mode). µ 6.
UPS Operation 58 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.
CHAPTER 5 COMMUNICATION The UPS is equipped with a communications interface port that allows communication with a wide variety of external devices including: S Video or dumb terminal S Serial printer S Computer with power management or shutdown software The serial port enables you to monitor and record diagnostic data with the following communication interfaces: S Serial Communications Interface Terminal Mode Data Dump Mode Printer Mode, 2400 Baud, with Novell Contacts (default) Printer Mode, 19200 Baud
Communication Front Panel Communications Access Before you access the front panel, review the following configurations and note the indicator that corresponds with the communication mode. NOTE Only the Printer mode front panel options change the baud rate. Use the UPS Serial Communications Menu to select other baud rates (see page 62).
Communication To access the front panel communication options, perform the following steps: 1. If the UPS is powered on, prepare your equipment for shutdown. Press and hold the Output Off button until the long beep ceases (approximately three seconds). µ The indicator remains lit indicating Normal mode, load offline. Switch the input breaker on the power processing unit to the OFF (O) position. Wait until all indicators turn off and then continue to the next step. 2.
Communication UPS Serial Communications Menu With the UPS Serial Communications (Main) Menu, you can view or select UPS communication modes, baud rates, and LAN configurations. To change or display the current communications configuration: 1. Connect the UPS serial port to a video monitor with a serial interface or to your computer’s serial port. If you are using OnliNet or LanSafe software, the UPS should already be connected to your computer. 2.
Communication Catalog #: Serial #: Version #: COMM mode: Baud x100: LAN mode: D15120112520 BK393B0274 02.00 Printer 024 Novell New COMM: New Baud: New LAN: Press space bar ASCII 096 Novell to continue NOTE Catalog #, Serial #, and Version # are all identification numbers unique to your UPS and can also be found on the UPS nameplate. 1 > Continuous Dump The UPS regularly transmits status information to the computer.
Communication SELECT LAN CONFIGURATION 1 2 3 4 Q > > > > > NOVELL AS400 3-COM/LAN MANAGER CUSTOM CONFIGURATION TO QUIT THIS MENU ENTER SELECTION >+> Select the AS400 option if you are using OnliSafe software to monitor the UPS. The Custom Configuration option has two screens: the first screen has options available for inverter shutdown, and the second screen has options available for the contact configuration.
Communication Z > Set Baud Rate allows you to select a new baud rate. The Select Baud Rate Menu displays a list of baud rate options. 2 4 5 6 7 8 Q > > > > > > > SELECT BAUD RATE 300 1200 2400 4800 9600 19200 QUIT THIS MENU ENTER SELECTION >-> 5. To save the configuration settings, type S at the Main Menu prompt. The UPS operates and communicates under the new configuration, and defaults to these settings each time it is started. If you want to abandon the selections you have made, type Q to quit.
Communication UPS Communications Interface Port In addition to configuring the UPS for specific communication options, you must also ensure proper use of the serial port when connecting the UPS to your network or monitoring equipment. NOTE Semiconductor switch contacts are rated at a maximum current of 50 mA and a maximum of 40 Vdc. Use only the pins specified for your communications configuration.
Communication Communications Mode Reference Chart The following chart defines the UPS serial port contacts. Serial communication is not available with 3Com and AS/400 network configurations. Use only the applicable pins for the selected communication mode; otherwise, interference problems may occur. Communication Mode Function Signal Name Pin No. True Condition Serial Data to UPS RS232 TxD 2 N/A Data from UPS RS232 RxD 3 N/A Signal Ground Novell (D f l ) (Default) 7 Battery On ON.
Communication 68 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.
CHAPTER 6 SPECIFICATIONS Prestige 6000 Specifications The following model specifications assume: S 88% efficiency at full load (Normal mode) Input power factor of 0.95 S 84% efficiency running on battery S Model 6000 UPS (Nominal Operating Specifications) Output VA Output Voltage Output Watts Input Current Output Current Normal (BTUs/hr) On Battery (BTUs/hr) 5000 200 3350 19.6A 25.0A < 1600 < 2200 5200 208 3500 19.7A 25.0A < 1600 < 2300 5500 220 3700 19.7A 25.
Specifications Model 4500 UPS (Nominal Operating Specifications) Output VA Output Voltage Output Watts Input Current Output Current Normal (BTUs/hr) On Battery (BTUs/hr) 3750 200 2500 14.6A 19.0A < 1200 < 1600 3900 208 2600 14.6A 19.0A < 1200 < 1700 4125 220 2750 14.6A 19.0A < 1300 < 1800 4300 230 2900 14.6A 19.0A < 1400 < 1900 4500 240 3000 14.6A 19.
Specifications Technical Specifications Input Voltage Range 170 to 276 Vac Input Power Factor 0.
Specifications Electrical Specifications for the Prestige 6000 with PPDM Use the following tables to determine load wiring requirements when the PPDM is used with the UPS. The distribution of your load on the available outputs of the PPDM may affect the maximum load obtainable.
Specifications Prestige 6000 PPDM Ratings with a Model 4500 UPS PPDM Model Input Utility Voltage and Selected UPS Output Voltage Input Current Output Voltage and Maximum Current Maximum Output Apparent Power** 208:120/208 Hardwired 220 Vac (60 Hz only) 24A 127/220 Vac (60 Hz only), 30.0/25.0A 4125 VA 208:120/208 Hardwired 208 Vac 24A 120/208 Vac, 30.0/25.0A 3900 VA 208:120 L5-30R 208 Vac 24A 120 Vac, 43.3A* 3900 VA 208:120/208 L6-20R 208 Vac 24A 120/208 Vac, 15.0/20.
Specifications 74 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.
CHAPTER 7 TROUBLESHOOTING The Prestige UPS is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Use the following troubleshooting chart to determine the UPS alarm condition. Indicator Legend Unlit Amber Green Flashing Condition Possible Cause Action UPS does not turn on. UPS is not connected correctly to the power source. Check connections to the power source. UPS input breaker is off. Reduce load, then reset breaker.
Troubleshooting Condition Possible Cause Action Remote Emergency Power-Off switch does not shut down the UPS. REPO switch is not wired properly. Check connections and contact your service representative. PowerPass Distribution Module does not deliver expected voltage. g Voltage Selector switch on the power processing unit is not set properly. Shut down the UPS (see page 53). Select proper voltage position (see page 41) and restart the UPS (see page 47).
Troubleshooting Condition Possible Cause Action Weak battery while in Bypass mode. This usually indicates that the batteries need replacing or the UPS requires service. Contact your service representative. Self Test failure. UPS internal problem. The UPS may switch to Bypass mode, depending on the circumstances. Reset the UPS by pressing the Output | On button until the alarm beeps. Contact your service representative if condition persists.
Troubleshooting Service and Support The troubleshooting chart on page 75 covers most of the difficulties you may encounter during normal operations. If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
INDEX Numeric 3Com Network Interface front panel configuration, 60 LAN Configuration Menu, 64 A AC Line Bypass switch, 54 operation, 54 alarm silencing, 77 UPS, 76 Alarm Conditions Battery Fault, 76 Overload, 76 Overtemperature, 76 Self Test Failure, 77 Utility Out of Spec, 76 AS/400 Network Interface front panel configuration, 60 LAN Configuration Menu, 64 ASCII Terminal Mode, 63 B battery circuit breaker, 26 configuration, 2 extension time, 3 input connector, 26 output connector, 26 storage, 23 Battery
Index Control Keys Control-C, 62 Control-E, 63 input cable connections, 43 output cable connections, 43 output wiring, 44 termination blocks, 45 cord, power, 36, 47, 71 Custom LAN Configuration Menu, 64 customer service, 78 D Data Dump Modes, 63 diagnostics, 52 Display Configuration Screen, 63 E exiting Main Menu, 65 hardwired PPU external battery connector, 31 input and output terminations, 33 input breaker, 31 input cable connections, 32 installation, 29 REPO switch, 35 output cable connections, 32
Index M O Operating Modes, 50 Main Menu, 62 Maintenance Bypass feature See also PowerPass Distribution Module (PPDM) activating, 54 deactivating, 56 Menu Custom LAN Configuration, 64 LAN Configuration, 64 Main, 62 Serial Communications, 62 Set Baud Rate, 65 Mode ASCII Terminal, 63 Battery, 51 Bypass, 51 Communications, 62 Data Dump, 63 Normal, 50 Printer, 61, 63 Terminal, 63 VT100 Terminal, 63 N Normal Mode, 50 indicator, 49 Novell Network Interface front panel configuration, 60 LAN Configuration Menu,
Index REPO connectors, 26 serial port, 26 Polled Dump Mode, 63 Power Management Software LanSafe, 60, 65 OnliNet, 60, 65 OnliSafe, 60, 64 PowerPass Distribution Module (PPDM) AC Line operation, 54 block diagram, 54 changing output voltage, 41, 56 hardwired input and output connections, 43 rear panel, 43 installation, 37 Maintenance Bypass feature, 37 operation, 54 plug/receptacle power output receptacles, 39 rear panel, 39 utility input connector, 39 startup, 47 Printer Mode front panel configuration, 61 M
Index troubleshooting chart, 75 tips, 48 U uninterruptible power system, 1 UPS alarm silencing, 77 alarms, 76 block diagram, 50 changing output voltage, 53 communication, 59 Communications Mode Reference Chart, 67 front panel, 49 hardwired PPU. See hardwired PPU operation, 49 operation with PPDM, 54 plug/receptacle PPU.
Index 84 Powerware® 9 Prestige Series User’s Guide (4500/6000 VA) S Rev H www.powerware.