Table 4. IRC Wire Terminations
IRC Terminal Function Remarks
J2-1 NC
Normal mode
J2-2 COM
J2-3 NO
J2-4 NC
Bypass mode
J2-5 COM
J2-6 NO
J2-7 NC
Battery mode
J2-8 COM
J2-9 NO
J2-10 NC
Alarm mode
J2-11 COM
J2-12 NO
NOTE Maximum contact rating: 250 Vac, 30 Vdc @ 5A; Wire range: 16–24 AWG
LanSafe Power Management Software
Each Eaton 9355 UPS ships with LanSafe Power Management Software and a
communication cable. To begin installing LanSafe software, see the instructions
accompanying the Software Suite CD.
NOTE Use only the supplied communication cable to connect the UPS to your computer.
LanSafe software provides up-to-date graphics of UPS power and system data and
power flow. It also gives you a complete record of critical power events, and it
notifies you of important UPS or power information. If there is a power outage and
the Eaton 9355 UPS battery power becomes low, LanSafe software can automatically
shut down your computer system to protect your data before the UPS shutdown
occurs.