User manual

5
MAU-00044/AD
ENGLISH
Troubleshooting (For further information, visit the www.eaton.com site or contact after-sales support.)


The battery backup outlets 6
are not supplied with power.
The connected devices are not
supplied when AC power fails.
AC power is available, but
the UPS operates on battery
power.
The ltered outlets 7 are not
supplied.
Problem Diagnostic Solution
Button 8 is not pressed.
The devices are not connected to
the battery backup outlets 6 .
Circuit breaker 10 , has been
tripped by an overload on the UPS
output.
The wall outlet is not supplied.
Circuit breaker 10 , has been
tripped by an overload on the UPS
output.
Press button 8 and check that it
turns green.
Connect the devices to the battery
backup outlets 6 .
Disconnect excess equipment
and reset the circuit breaker 10 by
pressing the corresponding button.
Supply power to the wall outlet.
Disconnect excess equipment
and reset the circuit breaker 10 by
pressing the corresponding button.
Green button 8 ashes:
- frequently.
-every 5 seconds
-every 2 seconds
-continually and the
audio alarm beeps
The UPS frequently operates on
battery power because the AC
power source is of poor quality
Have the electrical installation
checked by a professional or use
another wall outlet.
1
2
3
4
5
6
7
8
9
The UPS operates on battery
power, beginning of battery backup
time
The UPS operates on battery
power, end of battery backup time.
The battery has reached the end of
its service life.
Have the battery replaced.
Green button 8 is off and
the audio alarm beeps every
1 second.
A fault has occurred on the UPS.
The battery backup outlets 6 are
no longer supplied.
Green button 8 is on and
the audio alarm beeps every
1 second.
Call after-sales support.
Green LED 9 is off
Surge protection is no longer
provided.
Call after-sales support.
The telephone line is
disturbed or modem
access is not possible.
Surge protection on the telephone
line is no longer provided.
Disconnect the telephone line from
the wall outlet.
Call after-sales support.
The UPS battery backup outlets 6
are overloaded.
Disconnect excess equipment
connected to the battery backup
outlets 6 .