Datasheet

Rev 1 Page 2 of 3
Eaton 9130 700-6000VA Tower UPS Technical Specification
ELECTRICAL OUTPUT CHARACTERISTICS – NORMAL MODE
Model
PW9130G700T
-XL
PW9130G1000T
-XL
PW9130G1500T
-XL
PW9130G2000T
-XL
PW9130G3000T
-XL
PW9130G6000T
-XL
Rated apparent/active power 700VA/630W 1000VA/900W 1500VA/1350W 2000VA/1800W 3000VA/2700W 6000VA/5400W
Number of output phases 1 Phase
Transfer time No break (normal to stored energy)
Rated output voltage
700-3000VA: 230V Single Phase (default), 200*, 208**, 220, 240Vac (selectable)
*output de-rated by 20%, **output de-rated by 10%
6000VA: 230V Single Phase (default), 208*, 220, 240Vac (selectable)
*output de-rated by 10%
Voltage variation ±2%
Crest factor 3:1
Rated output frequency 50Hz (default) or 60Hz
Frequency regulation ±3Hz of nominal line frequency, ±0.5, ±1Hz, ±2Hz User Selectable (outside this range ±0.1Hz)
Total output voltage distortion <3% (Across a linear load); <5% (Across a non-linear load)
Number of output phases 1 Phase
Output Overload
(Normal Mode)
Level 1: 100-102%: Activates Overload alarm
Level 2: >102-130%: Load transfers to Bypass mode after 12 seconds (700-3000VA), 2 minutes (6000VA)
Level 3: >130-150%: Load transfers to Bypass mode after 2 seconds (700-3000VA), 30 seconds (6000VA)
Level 4: >150%: Load transfers to Bypass mode immediately
Short circuit capability: 5 cycles capability, then UPS shut down
NOTE: Default configuration transfers immediately to Bypass at >102%
Dynamic Voltage variation ±6% max from 100% to 20% load step or vice versa
ELECTRICAL OUTPUT CHARACTERISTICS – STORED ENERGY
Rated apparent/active power 700VA/630W 1000VA/900W 1500VA/1350W 2000VA/1800W 3000VA/2700W 6000VA/5400W
Waveform Sine Wave
Rated output voltage 230V Single Phase (default), 200*, 208**, 220, 240,Vac (selectable)
*200V output de-rated by 20%, 208V output de-rated by 10%
Output voltage variation ±2% (700-3000VA), ±3% (6000VA)
Crest factor 3:1
Rated output frequency
50Hz (default) or 60Hz
Output frequency regulation < ±0.1Hz
Total output voltage distortion <3% (Across a linear load); <5% (Across a non-linear load)
Load power factor range
0.7 – 1.0
Number of output phases 1 Phase
Output Overload
(Battery Mode)
Level 1: 100-102%: Activates Overload alarm
Level 2: >102-130%: 12 seconds (700-3000VA), 2 minutes (6000VA)
Level 3: >130-150%: 2 seconds (700-3000VA), 30 seconds (6000VA)
Level 4: >150%: UPS shuts down within 100ms
Short circuit capability: 5 cycles capability, then UPS shut down
EFFICIENCY (Input/Output)
At 100% load (On Line
Mode/High Efficiency Mode)
90% / >93% (700-2000VA), 91% / >93% (3000VA), >94% / >98% (6000VA)
At 100% load (On Battery) >79.5% (700VA), >82% (1000-1500VA), >84% (2000-3000VA), >92% (6000VA)
Dissipation normal mode 70W 100W 150W 200W 267W 345W
Dissipation on battery 163W 198W 296W 343W 514W 470W
BATTERY
Battery Type 12V, 7/9 Ah batteries, Valve Regulated Lead Acid, AGM
Battery Management Advanced Battery Management (ABM
®
) = 90% resting,10% floating/charging
Charging current 1.0A – 1.6A
Battery cut-off voltage 1.60VDC – 1.85VDC per cell depending on load
Battery Re-charge time
Internal Battery: <4 hours to recover 90 percent of nominal backup
+1 EBM: 9 hours, +2 EBMs: 15 hours, +3 EBMs: 21 hours, +4 EBMs:27 hours
Battery Nominal Voltage 24V (12 Cells) 36V (18 Cells) 48V (24 Cells) 96V (48 Cells) 96V (48 Cells) 240V(120 Cells)
UPS Battery Configuration 2 x 12V9Ah 3 x 12V9Ah 4 x 12V9Ah 8 x 12V9Ah 8 x 12V9Ah 20 x 12V7Ah
Battery Replacement Hot-swappable internal and external batteries