Remote Control Panels RCP100 & RCP200 Series Enclosure Power Distribution Units (ePDU™)
RCP100 Series RCP100-BLK-LT EMERGENCY POWER OFF (EPO) • RCP100-GRY: Locking (N/O) EPO button for PDUs with the standard 3 pin remote I/O port. Turn to reset • RCP100-GRY-LT: Locking (N/C) EPO button for PDUs with the latching (LT) option. Turn to reset. • Per European requirements, there is a yellow square behind the EPO button RCP100-GRY RACK MOUNTED • 19” x 1.73” x 2.0”, flush mounted, 18 GA.
Standard Remote Control Interface REMOTE START REQUIRES (2) CONDITIONS: 1. The “on/off/remote” switch must be in the “remote” position. 2. A maintained closure between pins 1 & 3 will turn the unit on. REMOTE POWER OFF REQUIRES (1) CONDITION: 1. Opening the maintained connection between pins 1 & 3 will turn off the switched outlets. REMOTE EPO REQUIRES (1) CONDITION: 1. A maintained contact between pins 2 & 3 will turn off the switched outlets regardless of the position of the “on/off/remote” switch.
RCP100-BLK-LT RCP100-GRY Drawings are not shown to scale Dimensions are in inches RCP200-GRY-LT RCP200-GRY 4 www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999 © 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.