Normal Mode Startup
To start up the UPS:
1. Verify that the maintenance bypass switch is in the UPS position
(see Figure 47 on page 81).
2. If an optional wall-mounted bypass cabinet is installed:
S Verify that the bypass breaker is in the OFF position (see
Figure 20 on page 32).
S Verify that the UPS breaker is in the ON position (see Figure 23
on page 36).
3. If an optional isolation transformer is installed, switch the input
circuitbreakertotheONposition(seeFigure12onpage21).
4. Switch on utility power where the UPS is connected.
5. Wait for the front panel LCD to illuminate.
The
indicator flashes.
6. Remove the breaker tie from all battery circuit breakers.
7. Switch all battery circuit breakers to the ON position.
The
indicator stops flashing.
8. Press any button on the front panel display to activate the menu
options.
9. Press the
button on the front panel display and then press the
button to select the TURN UPS ON/OFF menu.
10. Select the TURN UPS ON option. Press and hold the
button for
three seconds, until the UPS stops beeping.
The
indicator illuminates. The UPS is now powering the load.
If the
indicator is flashing, check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if
necessary.