Instruction Booklet IB158002EN Effective October 2014 Eaton SPD Max Series Surge Protective Device Contents Description Page 1.0 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.0 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3.0 Operating Features . . . . . . . . . . . . . . . . . . . . . 6 4.0 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . 8 5.0 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 9 6.0 Ordering Guidelines.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 1.0 Introduction 1.4 Catalog Numbering System 1.1 Manual Organization Each Eaton SPD Max Series unit has a name plate that identifies the parameters used for manufacture. These parameters are expressed in letters and numbers, to reflect the Series, kA Rating, Voltage Code, Feature Package, and Application, as shown in Table 1 and Table 5.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 1.5 Equipment Testing WARNING WARNING CONDUCTING DIELECTRIC, MEGGER, OR HI-POTENTIAL TESTING WITH THE SPD INSTALLED WILL CAUSE INTERNAL DAMAGE TO THE SPD. THE SPD WILL ALSO CAUSE THE TEST TO FAIL. Every Eaton SPD Max Series unit is tested at the factory for dielectric breakdown. No further SPD testing is required for installation.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 2.3 Installation Procedures 1. Before mounting the SPD Max Series device ensure that the mounting surface is sufficient to support the weight of the SPD. See Section 5.0 Specifications for weight. The SPD should be mounted as close as possible to the electrical cabinet and as close as possible to the wiring connection point within the electrical cabinet.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 2.3.1 Installation Procedures for Top Entry If bottom or side entry isn’t practical for the installation of the SPD Max, top entry can be accomplished using the following steps. Display Cable Lid Latches Cable Hold Down Brackets SPD Status Lid Latches SPD Status Cables Lid Latches Figure 3. SPD Max with Two SPDs and Circuit Breaker 1.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 5. Unscrew the Neutral and Ground terminal blocks from the enclosure base. Rotate the Ground terminal block 180o and mount the two terminal blocks in the mounting holes located on the bottom left of the unit. (See Figure 5) 3.0 Operating Features 3.1 General The Eaton SPD Max Series comes in two feature packages: Basic, and Standard with Surge Counter.
Eaton SPD Max Series Surge Protective Device The Basic Feature Package has the following features: • • Green LEDs: Illumination indicates the phase is fully protected, and operating normally, with all protection active and available. Green LEDs also indicate Neutral to Ground protection on units with a Neutral wire. Green LEDs do not indicate on/off status of power.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 4.0 Troubleshooting Many SPD failures result from improper installation. Once the SPD is installed properly, it is a highly reliable unit. The most common reason for SPD failure is a temporary overvoltage (TOV) condition. If the SPD does not function properly, first confirm that it is installed properly. See Section 2, Installation.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 5.0 Specifications Table 4.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 6.0 Ordering Guidelines Table 5.
Eaton SPD Max Series Surge Protective Device Instruction Booklet IB158002EN Effective October 2014 Figure 8. DELTA (3W + G) with Circuit Breaker Figure 9. Wye (4W + G) with Circuit Breaker * SPD2 only installed in models with S, U, W and Y suffixes. EATON www.eaton.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 RED RED RED RED RED RED Figure 10. High Leg Delta (4W + G) with Circuit Breaker Figure 11. Split Phase (3W + G) with Circuit Breaker * SPD2 only installed in models with S, U, W and Y suffixes. 12 EATON www.eaton.
Eaton SPD Max Series Surge Protective Device Instruction Booklet IB158002EN Effective October 2014 Figure 12. DELTA (3W + G) with Terminal Block Figure 13. Wye (4W + G) with Terminal Block * SPD2 only installed in models with S, U, W and Y suffixes. EATON www.eaton.
Instruction Booklet IB158002EN Eaton SPD Max Series Surge Protective Device Effective October 2014 RED RED RED RED RED RED Figure 14. High Leg Delta (4W + G) with Terminal Block Figure 15. Split Phase (3W + G) with Terminal Block * SPD2 only installed in models with S, U, W and Y suffixes. 14 EATON www.eaton.
Eaton SPD Max Series Surge Protective Device Instruction Booklet IB158002EN Effective October 2014 Figure 16. Product Dimensions EATON www.eaton.
Instruction Booklet IB158002EN Effective October 2014 7.0 Warranty Eaton warrants these products for a period of 15 years from the date of delivery to the purchaser, 20 years if the product is properly registered with Eaton, to be free from defects in both workmanship and materials. To register a SPD MAX with Eaton please go to www. eaton.com/spd and click on the SPM Series Product Registration link on the SPD MAX page.