Cut Sheet

8
Technical Data TD01005025E
Effective June 2010
Eaton’s SPD Series for mounting external to
electrical distribution equipment
EATON CORPORATION www.eaton.com
Table 32. 50 kA Unit VPR (Cat. No. Ends with 1O or 1Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 800 1200 700 1500
208Y and 220Y 800 1200 700 1500
400Y and 480Y 1200 2000 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 800 1200 700 1500
Table 33. 80–100 kA Unit VPR (Cat. No. Ends with 1O or 1Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 800 900 700 1500
208Y and 220Y 800 900 700 1500
400Y and 480Y 1200 1200 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 800 900 700 1500
Table 34. 120–200 kA Unit VPR (Cat. No. Ends with 1O or 1Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 800 900 700 1500
208Y and 220Y 800 900 700 1500
400Y and 480Y 1200 1200 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2500
600D N/A 2500 N/A 2500
240H 800 900 700 1500
Table 35. 250–300 kA Unit VPR (Cat. No. Ends with 1O or 1Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 800 900 700 1500
208Y and 220Y 800 900 700 1500
400Y and 480Y 1200 1500 1200 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 1800 N/A 2000
600D N/A 2500 N/A 2500
240H 800 900 700 1500
Table 36. 400 kA Unit VPR (Cat. No. Ends with 1O or 1Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 800 900 700 1500
208Y and 220Y 800 900 700 1500
400Y and 480Y 1200 1500 1200 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 1800 N/A 2000
600D N/A 2500 N/A 2500
240H 800 900 700 1500
Table 37. 50 kA Unit VPR (Cat. No. Ends with 2O, 2Q, 3O, or 3Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 900 1500 700 1500
208Y and 220Y 900 1500 700 1500
400Y and 480Y 1200 2000 1000 2500
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 2500 N/A 2500
240H 900 1500 700 1500
Table 38. 80–100 kA Unit VPR (Cat. No. Ends with 2O, 2Q, 3O, or 3Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 900 900 700 1500
208Y and 220Y 900 900 700 1500
400Y and 480Y 1200 1200 1000 2500
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 2500 N/A 2500
240H 900 900 700 1500
Table 39. 120200 kA Unit VPR (Cat. No. Ends with 2O, 2Q, 3O, or 3Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 900 900 700 1500
208Y and 220Y 900 900 700 1500
400Y and 480Y 1200 1200 1000 1800
600Y 1500 1500 1500 2500
240D N/A 1000 N/A 1000
480D N/A 2500 N/A 2500
600D N/A 2500 N/A 2500
240H 900 900 700 1500
Table 40. 250300 kA Unit VPR (Cat. No. Ends with 2O, 2Q, 3O, or 3Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 800 900 700 1500
208Y and 220Y 800 900 700 1500
400Y and 480Y 1200 1200 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2000
600D N/A 2500 N/A 2500
240H 800 900 700 1500
Table 41. 400 kA Unit VPR (Cat. No. Ends with 2O, 2Q, 3O, or 3Q)
Voltage Code
Protection Mode
L-N L-G N-G L-L
240S 800 900 700 1500
208Y and 220Y 800 900 700 1500
400Y and 480Y 1200 1200 1000 2000
600Y 1500 1500 1200 2500
240D N/A 1000 N/A 1000
480D N/A 2000 N/A 2000
600D N/A 2500 N/A 2500
240H 800 900 700 1500
VPR data for units in a NEMA 4 or 4X enclosure with an internal disconnect (catalog number ends with O or Q)