3.2.2 Standard Feature Package
The Eaton SPD Series Standard Feature Package display is
shown in Figure 15.
Figure 15. Standard Feature Package Display
The Standard Feature Package has the following features:
All features of the Basic Feature Package.
One Form C relay contact rated at 150Vac or 125Vdc @1A.
Normal operating conditions. N.O. = OPEN. N.C =
CLOSED.
Loss of protection on any phase or loss of power. N.O. =
CLOSED. N.C. = OPEN.
Audible alarm with Reset push button.
EMI/RFI filtering.
3.2.3 Standard With Surge Counter Feature Package
The Eaton SPD Series Standard With Surge Counter Feature
Package display is shown in Figure 16.
Figure 16. Standard With Surge Counter Feature Package
Display
The Standard With Surge Counter Feature Package has the fol-
lowing features:
All features of the Standard Feature Package.
LCD screen that displays surge count.
Reset button to RESET the surge counter to zero.
3.2.4 SPD Display Rotation
The SPD display can be rotated on the SPD enclosure, up to 360
degrees. This allows you to position the display for the best vis-
ibility regardless of the position in which the SPD is installed.
Rotations are at 90, 180, and 270 degrees.
Reposition the SPD display as follows:
1. Remove power from the unit.
2. Remove and discard the perforated overlay material at the
two opposite corners of the display.
3. Remove the two phillips head screws that hold the display.
4. Rotate the display to the desired position. Be careful not to
overstress the display ribbon cable.
5. Place the display back onto the SPD enclosure. Again, be
careful not to overstress or crimp the ribbon cable.
6. Replace the two phillips head screws. Tighten screws to
1.35 Nm (12 in-lbs).
7. Restore power to the unit.