Operator`s manual

Eaton T2235 Series eATS ePDUs P-164000014—Rev 1 www.eaton.com/ePDU 21
Chapter 6 Specifications
This chapter lists specifications that are applicable for all Eaton T2235 Series Automatic Transfer Switch (eATS)
Enclosure Power Distribution Unit (ePDU) models. This chapter also describes online access to detailed model
specifications, mechanical engineering diagrams, and additional documentation, such as product feature,
options, and support.
Technical Specifications
This section includes technical specifications that apply for all T2235 Series eATS ePDUs, including mechanical
and environmental specifications, input and output specifications, and safety standards.
Mechanical Specifications
Table 5 provides mechanical specifications for all T2235 Series eATS ePDUs.
Environmental Specifications
Table 6 provides environmental specifications for all T2235 Series eATS ePDUs.
Input and Output Specifications
Table 7 provides electrical input and output specifications for all T2235 Series eATS ePDUs.
Table 5. Mechanical Specifications
Width 482.6 mm (19.0”)
Height 44.5 mm (1.75”)
Chassis Depth 177.8–24.3 mm (7.0”–9.5”)
Approximate Shipping Weight 6.8 kg (15 lb.)
Mounting Rackmount
Finish Powder coat black with white silk screen or zinc plated gold with black silk screen
Rack Sizing Standard 19” rack
Table 6. Environmental Specifications
Operating Temperature (Room Ambient) 0°C to 50°C (32°F to 122°F)
Shipping and Storage Temperature -25°C to 70°C (-13°F to 158°F)
Interior ePDU Temperature Maximum 70°C (158°F) maximum
Relative Humidity 5–90% noncondensing
Operating Altitude
Up to 3,048m (10,000 ft) above sea level
(derated for higher altitude applications)
Shipping and Storage Altitude Up to 12,200m (40,000 ft) above sea level
Table 7. Input and Output Specifications
Input Frequency 50/60 Hz ±3Hz
Input Voltage Tolerance +6% / -10%
Input Power Range 1.4kW–5kW
Output Frequency 50/60 Hz
Output Voltage Tolerance +6% / -10%
Output Voltage Range 100–240V (12A, 16A, or 24A)