Instruction manual

164201603-3 1 of 2
PHYSICAL FEATURES AND REQUIREMENTS
021509D
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
BATT
COMP
UPS
1
2
3
4
5
6
FRONT
TOP
VIEW
INSTALLATION INFORMATION
Eaton
®
9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4 www.eaton.com/powerquality
A-4
1. The UPS equipment operating environment must meet the weight requirements shown in
Table A and the size requirements shown on Drawing 164201603-11.
2. The UPS cabinet is palleted separately from accessory cabinets for shipping. The 9390IT
UPS models with interanl battery configuration ship with batteries installed.
3. Do not tilt cabinets more than "10° during handling.
4. Dimensions are in millimeters (inches).
5. The standard 9390 cabinets can be installed in line‐up‐and‐match or standalone
configurations. The 9390IT UPS with internal battery configuration is standalone only.
Table A. Standard 9390/9390IT UPS Cabinet Weight
Model
Weight
kg (lb)
Shipping Installed Point Loading
Powerware
9390/9390IT-40/20
Powerware
9390/9390IT-40/30
Powerware
9390/9390IT-40/40
231 (508) 208 (458) 4 at 52.2 (115)
Powerware 9390-80/40
Powerware 9390-80/50
Powerware 9390-80/60
Powerware 9390-80/80
313 (690) 290 (640) 4 at 72.5 (160)
271 (618) 258 (568) 4 at 64.5 (142)
Table B. 9390IT UPS with Internal Battery Configuration Cabinet Weight
Model
Weight
kg (lb)
No batteries 2-string
batteries
3-string
batteries
Point Loading
(see diagram below)
Powerware 9390IT-40/20
Powerware 9390IT-40/30
Powerware 9390IT-40/40
318 (699) 541 (1189) 657 (1445)
1 & 2134.7 (296.5)
3 & 4135.9 (299.0)
5 & 6 57.7 (127.0)
NOTE: For shipping add 23 (50).