Instruction manual

NOTE 1. All building alarm inputs require an isolated normally‐open or
normally‐closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown.
Building alarm inputs can be programmed for use with either normally‐open
or normally‐closed contacts. All control wiring and relay and switch contacts
are customer‐supplied.
2. The building alarms can be programmed to display the alarm functional
name.
091505A
164201603-10
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
MINI‐CSB INTERFACE TERMINALS
1
8
P5
BUILDING ALARM
#3
BUILDING ALARM #3 RTN
MINI‐CSB
4 of 15
BUILDING ALARM
#4
BUILDING ALARM
#5
BUILDING ALARM
#6
BUILDING ALARM #4 RTN
BUILDING ALARM #5 RTN
BUILDING ALARM #6 RTN
INSTALLATION INFORMATION
Eaton
®
9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4 www.eaton.com/powerquality
A-49