Instruction manual

091505A
164201603-10
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
NOTE This drawing is for parallel wiring purposes and is not a floor layout plan.
UPMs can be placed in any physical order.
PARALLEL SYSTEM CAN (PULL CHAIN) WIRING
UPM
1
UPM
2
UPM
3
UPM
4
CAN
(IF INSTALLED)
(IF INSTALLED)
PULL CHAIN
PARALLEL SYSTEM CAN WIRING
10 of 15
TWISTED PAIR
TWISTED PAIR
TWISTED PAIR
UPM 1
CAN CARD J3
UPM 2
CAN CARD J3
UPM 3
CAN CARD J3
(IF INSTALLED)
UPM 4
CAN CARD J3
(IF INSTALLED)
INSTALLATION INFORMATION
Eaton
®
9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4 www.eaton.com/powerquality
A-55
CAN Wiring Terminations
From UPM 1 CAN Card To UPM 2 CAN Card
To UPM 3 CAN Card
(If Installed)
To UPM 4 CAN Card
(If Installed)
J3–8 (L) J3–8 (L) J3–8 (L) J3–8 (L)
J3–9 (H) J3–9 (H) J3–9 (H) J3–9 (H)
J3–10 (Shield) J3–10 (Shield) J3–10 (Shield) J3–10 (Shield)