Instruction manual

USING THE CONTROL PANEL
Eaton
®
9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4 www.eaton.com/powerquality
8-3
8.2 Using the Main Menu
The UPS main menu bar allows you to display data in the information area to help you
monitor and control UPS operation. The following menus and options are available:
Menu Option Description
EVENTS Displays the list of Active System Events and a historical log of system events.
METERS Displays performance meters for the system or critical load.
CONTROLS Displays the System Controls screen.
SETUP Allows you to set the display contrast, set the date and time for the time stamp,
configure the UPS serial communication ports, and view the firmware version numbers.
LOAD OFF De-energizes the critical load and powers down the UPS.
Returns to Main Menu and Mimic screen from the Events, Meters, Controls, or Setup
screens. Returns to the main System Setup Level screen from a setup submenu.
8.2.1 Mimic Screen
Figure 8‐3 shows the Main Menu and Mimic screen. To select the Mimic screen from
the Events, Meters, Controls, or Setup screens, press the
pushbutton on the
current menu bar.
The Mimic screen shows the internal components of the UPS cabinet and a real‐time
graphical representation of the operating status of the system.
In Energy Saver mode, all Mimic lines show as active (double lines). If the input
breaker is opened or the input feed is out of limits, the input will show as a single line.
TIME: 11 : 35 : 43 DATE: 02 / 25 / 2004
CONTROLS LOAD OFF
METERSEVENTS SETUP
OUTPUT
BATT
UPS
INPUT
STSW
BYPASS
Figure 8‐3. Main Menu and Mimic Screen (Normal Mode)