Data Sheet

DATASHEET - XIO-EXT121-1
Expansion for compact PLC XC-CPU121, 10DI, 8DI/DO(T), 6AI, 2AO
Part no. XIO-EXT121-1
Catalog No. 290450
Delivery program
UL/CSA approval
Shipping classification (DNV, GL, ABS, BV, LR)
expandable with XI/OC signal modules (except XIOC-NET-DP-M)
plug in spring-cage terminals
Description Local I/O expansion for PLC XC121
Inputs expansion (number) Digital: 10; of which can be used as interrupts: 6; analog: 6 (0 - 10V: 2 or 0 - 20 mA: 2
or Pt100: 2)
Digital: An additional 8 (also usable as outputs)
Outputs expansion (number) Digital: 8 (also usable as inputs)
Analog: 2 (0 - 10 V)
Technical data
General
Standards IEC/EN 61131-2
EN 50178
Ambient temperature °C 0 - +55
Storage ϑ °C -25 - +70
Mounting position Horizontal
Relative humidity, non-condensing (IEC/EN 60068-2-30) % 10 - 95
Air pressure (operation) hPa 795 - 1080
Vibration resistance Frequency 5 - 9 Hz; amplitude 3.5 mm
9 - 150 Hz; 1.0 g constant acceleration
Mechanical shock resistance g 15
Shock duration 11 ms
Overvoltage category/pollution degree II/2
Degree of Protection IP20
Rated insulation voltage U
i
V 500
Emitted interference EN 61000-6-4
Interference immunity EN 61000-6-2
Weight kg 0.15
Connection
X1 plug
Plug type Spring-loaded terminal block, 20-pole, B2L 3.5 (Weidmüller)
Terminal capacity (solid)
mm
2
Terminal capacity, solid/stranded
mm
2
0.5 - 1
X2/X3 plug
Plug type Spring-loaded terminal block, 10-pole, BLZF 3.5/180 or BLI/O 3.5/10F with LEDs
(Weidmüller)
Terminal capacity (solid)
mm
2
Terminal capacities
mm
2
0.5 - 1
Power supply
Hold-up time on supply drop-out
Duration of dip ms 10
Repetition rate s 1
Input voltage V DC 24
Admissible range V DC 20.4 - 28.8
Power consumption W max. 1.68
Input current mA 70
Residual ripple % ≦ 5
Maximum power loss (without local I/O) P
v
W 1.7
Overvoltage protection Yes
06/18/2021 Eaton 290450 ED2021 V80.0 EN 1 / 5