Datasheet

03/19/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 7
Overload�relay�2,4�-�4A
Part�no. ZB32-4
Article�no. 278449
Program
Product range Overload relay ZB up to 150 A
Phase-failure sensitivity IEC/EN 60947, VDE 0660 Part 102
Description Test/off button
Reset pushbutton manual/auto
Trip-free release
Mounting type Direct mounting
I
r
A 2.4 - 4
Contact sequence
Auxiliary contacts
N/O = Normally open 1 N/O
N/C = Normally closed 1 N/C
For use with DILM17, DILM25,
DILM32,
DILM38,
DILMF8
DILMF11
DILMF14
DILMF17
DILMF25
DILMF32
DIULM17, DIULM25,
DIULM32,
SDAINLM30,
SDAINLM45,
SDAINLM55
Short-circuit protection
Type “1” coordination gG/gL A 25
Type “2” coordination gG/gL A 16
Notes
Overload release: tripping class 10 A
Short-circuit protection: Observe the maximum permissible fuse of the contactor with direct device mounting.
Suitable for protection of Ex e-motors.
II (2) GD
PTB 10 ATEX 3010
Observe manual AWB2300-1527D/GB.
Notes
Fitted directly to the contactor Separate mounting

Summary of content (7 pages)