Datasheet

03/26/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 5
Overload�relay�2,4�-�4A
Part�no. ZE-4
Article�no. 014518
Program
Product range ZE overload relays for mini contactor relays
Phase-failure sensitivity IEC/EN 60947, VDE 0660 Part 102
Description Test/off button
Reset pushbutton manual/auto
Trip-free release
Mounting type Direct mounting
Setting�range
Overload releases I
r
A 2.4 - 4
Contact sequence
Auxiliary contacts
N/O = Normally open 1 N/O
N/C = Normally closed 1 N/C
For use with DILEM
DIULEM/21/MV
SDAINLEM
Short-circuit protection
Type “1” coordination gG/gL A 20
Type “2” coordination gG/gL A 10
Notes
Overload release: tripping class 10 A
Short-circuit protection: Observe the maximum permissible fuse of the contactor with direct device mounting.
Suitable for protection of Ex e-motors
II (2) GD
PTB 10 ATEX 3014
Observe manual AWB2300-1425D/GB.
Notes
When fitted directly to the contactor a clearance of at least 5mm is required between the overload relays.
1 Contactor
Approbationen
UL approval Yes
CSA approval Yes
Product Standards UL 508; CSA-C22.2 No. 14; IEC/EN 60947-4-1; CE marking
UL File No. E29184
UL CCN NKCR
CSA File No. 12528
CSA Class No. 3211-03
NA Certification UL listed, CSA certified
Specially designed for NA No
Suitable for Branch circuits
Max. Voltage Rating 600 V AC