Drawing : - TPC433 Issue :-1 Date : - 21/05/15 RM85H INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 RM85H PACKAGE CONTENTS Item Description Quantity 10560RH-US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube – 3/8” I/D 7.
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 INTRODUCTION Designed for a wide range of applications, the RM85 is a rugged, industrial unit, which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 SPECIFICATIONS MODEL: 10560rg-us HEIGHT: 37.2” (945mm) WIDTH: 21.5” (545mm) DEPTH: 19.4” (492mm) WEIGHT: 99 lbs (45 Kg) AIRFLOW: 230 CFM (390 M3/hr) POWER SUPPLY: 110V/ 60Hz/ 1 ph FINISH: Rotational Moulded polyethylene OPERATING RANGE: 33°F – 95°F REFRIGERANT: R-407c (17.6 oz) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 OPERATION The following procedures should be followed to test the RM85H for correct operation: 1. After unpacking, examine all external features to confirm damagefree shipment. Report all defects and damage at once. Connect the power cable to a grounded 15 Amp electrical outlet. 2. Setting the Digital Humidistat The Digital Humidistat is factory preset to give the optimum level of control. Only adjustment of the desired set point is required.
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 F. When the unit is operated in ambient of less than 59°F, a defrost cycle should occur approximately every ½ hour. The exact time is impossible to predict as the unit is fitted with a temperature sensitive defrost control. During this defrost cycle the fan will switch off. When the unit is defrosting, the % Relative Humidity displayed on the digital controller may increase as a result of the ice / frost melting.
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 ROUTINE MAINTENANCE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE MAINTNENANCE ON ITEMS 1, 2, 3, 4 & 5 To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 TROUBLESHOOTING SYMPTOM CAUSE 1. No power to unit Unit inoperative 2. Humidity Control set too high 1. Fan motor burnt out 2. Dirty refrigeration coils 3. Loose electrical wiring Little or no airflow Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Little or no defrost when required 1. Faulty timer 2. Faulty by-pass valve Unit vibrates excessively 1. Loose compressor 2.
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 RM85 SPARE PARTS LIST NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 13 14 16 17 18 19 20 21 DESCRIPTION Timer Condenser coil Evaporator coil Cable & Tube wrap Drain tray Filter Capillary Solenoid valve Filter dryer Compressor Defrost Relay Solenoid coil Humidity Controller Run capacitor On/Off switch Power Relay Pump purge switch Fan Fan inlet ring Wheel Rubber foot Condensate pump Page 10 of 12 PART NUMBER 1619508 2029322 2029323 2056002 2056003 2056004 3014254
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 Page 11 of 12
Drawing : - TPC433 Issue :-1 Date : - 21/05/15 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.