Data Sheet

Product Data Sheet 6314/2TDHHP
02/04/2019 page 5 of 11
Information to the curve:
0% - <=7% PWM: 0 1/min
7% - 10% PWM: 1.000 1/min (corresponding to min. speed)
10% - 90% PWM: linear increasing curve
90% - 100% PWM: 7.000 1/min (corresponding to max. speed)
7% PWM: 1.000 1/min (Fan on, comming from 0% PWM)
7% - 5% PWM: linear decreasing curve (von 100% PWM kommend)
5% PWM: 800 1/min or 0 1/min (Fan off, comming from 100% PWM)
Transistor requirements:
Vce max. >= 12V; Isink max. >=5mA; Vce sat. <= 0,15V
3.2 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/- 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.
p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Name
Condition
PWM 0001
PWM: 95 %; f: 2 kHz
>90% PWM; f = 2 kHz or broken lead wire (open control input)
Features
Condition
Symbol
Values
Voltage range
U
16 V
36 V
Nominal voltage
U
N
24,0 V
Power consumption
p = 0
PWM 0010
P
37 W
70 W
16,0 W
Tolerance
+- 10 %
+- 10 %
+- 10 %
Current consumption
p = 0
PWM 0010
I
2.300 mA
2.800 mA
1.850 mA
Tolerance
+- 10 %
+- 10 %
+- 10 %
Speed
p = 0
PWM 0010
n
5.750 1/min
7.000 1/min
7.000 1/min
Tolerance
+- 7,5 %
+- 5 %
+- 5 %