Product Data Sheet RLF100-11/14 Product Data Sheet RLF100-11/14 The engineer's choice
Product Data Sheet RLF100-11/14 RLF100-11/14 INDEX 1 General ...................................................................................................................................................................... 3 2 Mechanics ................................................................................................................................................................. 3 2.1 2.2 3 Operating Data ..........................................................................
Product Data Sheet RLF100-11/14 1 General Fan type Rotating direction looking at rotor Airflow direction Bearing system Mounting position - shaft 2 Mechanics 2.1 General Width Height Depth Mass Housing material Impeller material Max. torque when mounted across both mounting flanges Screw size 2.
Product Data Sheet RLF100-11/14 3 Operating Data 3.1 Electrical Operating Data Measurement conditions: ∆p = 0: I: Features Voltage range Nominal voltage Power consumption Normal air density = 1,2 kg/m3; Temperature 23°C +/- 3°C; Motor axis horizontal; warm-up time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area should not be any solid obstruction within 0,5 m. corresp. to free air flow (see chapter aerodynamics) corresp. to arithm.
Product Data Sheet RLF100-11/14 Locked Rotor Protection: Locked Rotor protection by cyclical shut down of the output stage. Interlock current at Un @ T3 3.3 Aerodynamics Measurement conditions: Measured with a double chamber intake rig acc. to DIN EN ISO 5801. Normal air density = 1,2 kg/m3; Temperature 23°C +/- 3°C; In the intake and outlet area should not be any solid obstruction within 0,5 m. Motor shaft horizontal.
Product Data Sheet RLF100-11/14 3.4 Sound Data Measurement conditions: Sound pressure level: 1 meter distance between microphone and the air intake. Sound power level: Acc. to DIN 45635 part 38 (ISO 10302) Measured in a semianchoic chamber with a background noise level of Lp(A) < 5 dB(A) For further measurement conditions see chapter aerodynamics. a.) Operation condition: 5.
Product Data Sheet RLF100-11/14 Result Below limit Class B Kind According Ceck accuracy / Limit Result Electrostatic Discharge Immunity Test DIN EN 61000-4-2:2001-12 Contact Discharge +/- 4 kV; Air Discharge +/- 8 kV B: The monitored function may deviate from designed performance to a specified level during exposure to a disturbance or revert to a fail safe mode or operation, but shall return to normal operation after the disturbance is removed.
Product Data Sheet RLF100-11/14 5 Safety 5.1 Electrical Safety Dielectric strength DIN EN 60950 (VDE 0805) and DIN EN 60335 (VDE 0700) A.) Type test Measuring conditions: After 48h of storage at 95% R.H. and 25°C. No arcing or breakdown is allowed! All connections together to ground. B.) Routine test Measuring conditions: At indoor climate. No arcing or breakdown is allowed! All connections together to ground. Isolation resistance Measuring conditions: After 48h of storage at 95% R.H.