User Manual

Operating instructions
A4D500-AM01-03
Translation of the original operating instructions
3.2 Nominal data
Motor M4D110-GF
Phase 3~ 3~ 3~ 3~
Nominal voltage / VAC 230 230 277 400
Connection Δ Δ Δ Y
Frequency / Hz 50 60 60 50
Type of data definition ml ml ml ml
Valid for approval /
standard
CE CE CE CE
Speed / min
-1
1350 1510 1590 1350
Power input / W 690 950 1050 690
Current draw / A 2.34 2.77 2.72 1.35
Max. back pressure / Pa 155 145 160 155
Min. ambient temperature
/ °C
-40 -40 -40 -40
Max. ambient
temperature
/ °C
65 60 60 65
Starting current / A 17.3 16.6 10
Maximum safe operating
speed / min
-1
1920
@ 55 °C
1920
@ 55 °C
1920
@ 55 °C
1920
@ 55 °C
Phase 3~ 3~
Nominal voltage / VAC 400 480
Connection Y Y
Frequency / Hz 60 60
Type of data definition ml ml
Valid for approval /
standard
CE CE
Speed / min
-1
1510 1590
Power input / W 950 1050
Current draw / A 1.6 1.57
Max. back pressure / Pa 145 160
Min. ambient temperature
/ °C
-40 -40
Max. ambient
temperature
/ °C
60 60
Starting current / A 9.6
Maximum safe operating
speed / min
-1
1920
@ 55 °C
1920
@ 55 °C
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Data according to ErP directive
Installation category A
Efficiency category Static
Variable speed drive No
Specific ratio
*
1.00
*
Specific ratio = 1 + pfs / 100 000 Pa
Actual Request
2013
Request
2015
Overall efficiency ηes / % 33.3 28.5 32.5
Efficiency grade N 40.8 36 40
Power input Pe / kW 0.66
Air flow qv / m³/h 5985
Pressure increase total psf / Pa 134
Speed n / min
-1
1355
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised
measurement configuration.
3.4 Technical features
Mass 9.8 kg
Size 500 mm
Surface of rotor Coated in black
Material of terminal box PC / ABS plastic
Material of blades Press-fitted sheet steel blank, sprayed
with PP plastic
Number of blades 5
Direction of air flow "V"
Direction of rotation Counter-clockwise, seen on rotor
Type of protection IP 54
Insulation class "F"
Humidity class F4-1
Mounting position Shaft horizontal or rotor on bottom; rotor
on top on request
Condensate discharge
holes
Rotor-side
Operation mode S1
Motor bearing Ball bearing
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
<= 3.5 mA
Electrical leads Via terminal box
Motor protection Thermal overload protector (TOP)
brought out
Cable exit Axial
Protection class I (if protective earth is connected by
customer)
Product conforming
to standard
EN 61800-5-1; CE
Approval CCC; EAC; UL 1004-1; VDE; CSA
C22.2 Nr.100
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
Item no. 10593-5-9970 · Revision 82543 · Release 2014-05-08 · Page 5 / 11
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com