Owner's manual

Operating instructions
D3G283-AB37-01
Translation of the original operating instructions
4.5 Connection screen
No. Conn. Designation Colour Function / assignment
1 1, 2 PE green/
yellow
Protective earth
1 3, 4, 5 L1, L2, L3 black Supply voltage 50 / 60 Hz
1 6 COM white 1 Floating status contact, break for failure (2 A, max. 250 VAC, min. 10 mA, AC1)
1 7 NC white 2 Floating status message contact, break for failure
2 8 0 - 10 V yellow Control input, set value 0 - 10 VDC, impedance 100 kOhm, SELV
2 11 + 10 V red Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for ext. devices (e.g. potentiometer),
SELV
2 12 GND blue Reference mass for control interface, SELV
Item no. 50383-5-9970 · Revision 82547 · Release 2014-05-08 · Page 8 / 11
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com