Manual
Operating instructions
G1G170-AB53-80
Translation of the original operating instructions
You can control the blower either via the 0-10 VDC input or the
PWM input. Note: Inputs cannot be used simultaneously.
3.2 Nominal data
Motor M1G074-CF
Phase 1~
Nominal voltage in VAC 230
Frequency in Hz 50/60
Type of data definition fa
Speed in min
-1
5830
Power input in W 360
Current draw in A 1.6
Min. ambient
temperature in °C
-25
Max. ambient
temperature in °C
+55
Min. temp. of flow
medium in °C
-25
Max. temp. of flow
medium in °C
+80
ml = max. load · me = max. efficiency · fa = running at free air
cs = customer specs · cu = customer unit
Subject to alterations
3.3 Data acc. to ErP Directive
Installation category A
Efficiency category Static
Variable speed drive integrated Integrated
Specific ratio
*
1,02
*
Specific ratio = 1 + pfs / 100 000 Pa
Actual Request
2013
Request
2015
Overall efficiency ηes 58,8 42 45
Efficiency grade N 74,8 58 61
Power input Ped in kW 0,3
Air flow qv in m³/h 285
Pressure increase total psf in Pa 2000
Speed n in min
-1
6220
Data established at point of optimum efficiency
3.4 Technical description
Mass 4.5 kg
Size 170 mm
Surface of rotor Coated in black
Material of protective
cover
Polyflam RPP 374-ND CS1 (UL 97-V0)
Material of impeller Aluminium sheet
Housing material Die-cast aluminium
Direction of rotation Clockwise, seen on rotor
Type of protection IP 20
Insulation class "B"
Mounting position Any
Cooling bore / aperture Rotor-side
Operation mode S1
Premix If gas is premixed in the blower, a
special blower must be used. Contact us
for details.
Motor bearing Ball bearing
Technical features - Tach output
- Output 10 VDC, max. 10 mA
- Motor current limit
- PFC, active
- Control input 0-10 VDC / PWM
- Over-temperature protected motor
Leakage current <= 3.5 mA
Electrical leads With plug
Motor protection Thermal overload protector (TOP) wired
internally
Approval UL 507; CSA C22.2 Nr.113; CCC
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.5 Mounting data
For depth of screw, see chapter 3.1 Graphic rendition of products
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
3.6 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
+80 °C
Min. permissible
ambient motor temp.
(transp./storage)
-40 °C
3.7 Electromagnetic compatibility
EMC interference
immunity
Acc. to EN 61000-6-2 (industrial
environment)
EMC interference
emission
Acc. to EN 61000-6-4 (industrial
environment)
EMC harmonics Acc. to EN 61000-3-2/3
Item no.: 51177-5-9970 · Revision: 73287 · Print-out: 2012-04-11 · Y. Uhlmann (VM-TDO) · Page 6 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 7938 81-0 · Fax +49 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com