4.5 Connection screen
No. Conn. Designation Colour Function / assignment
1 1 PE green/
yellow
Ground wire
1 3 L1 black Supply voltage, 50/60 Hz
1 4 L2 black Supply voltage, 50/60 Hz
1 5 L3 black Supply voltage, 50/60 Hz
1 6 COM white 1 Floating status message contact, normally closed connection (2 A, max. 250 VAC, min. 10 mA,
AC1)
1 7 NC white 2 Floating status message contact, normally closed connection
2 8 0-10 V yellow Control input, set value 0-10 VDC, impedance 100 kΩ, SELV
2 10 P orange Do not use
2 11 +10 V red Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for external devices (e.g.
potentiometer), SELV
2 12 GND blue Reference mass for control interface, SELV
Item no. 50140-5-9970 · Revision 82547 · Release 2014-05-08 · Page 9 / 12